TROUBLESHOOTING
GUIDE
(cont)
SYMPTOM
PROBABLE
CAUSE
REMEDY
System
noises
Piping
vibration
5
Support
piping
as
required.
Check
for
loose
pipe
connectors.
Expansion
valve
hissing
Add
refrigerant.
Check
for
plugged
liquid
line
strainer.
Compressor
noisy
Check
valve
plates
for
valve
noise.
Replace
compressor
(worn
bearings).
Check
for
loose
compressor
holddown
bolts.
Freeze-up
improper
charging
Make
sure
that
a
full
quantity
of
water
is
flowing
thru
the
cooler
while
charging
and
that
suction
pressure
in
cooler
is
equal
to
or
greater
than
that
corresponding
to
32
F
(58
psig
for
Refrigerant
22).
Improperly
set
safety
thermostat
Check
safety
thermostat
for
proper
setting
at
beginning
of
each
season.
Operating
with
safety
thermostat
bypassed
If
thermostat
was
bypassed
for
checking,
be
sure
it
is
back
in
the
circuit
before
starting
the
unit.
Improper
circulation
of
chilled
water
Use
ample
size
cleanable
strainer
in
the
chilled
water
circuit.
Make
sure
strainer
is
clean.
It
may
some¬
times
be
necessary
to
chemically
treat
the
water
to
prevent
forma¬
tion
of
deposits.
System
not
drained
for
winter
shutdown
Remove
drain
plugs
at
end
of
cooling
season.
Blow
out
any
residual
water.
Instead
of
drain¬
ing,
a
suitable
antifreeze
may
be
added
to
the
water.
Damage
to
the
chiller
due
to
freezing
is
considered
abuse
and
may
affect
the
warranty.
Hot
liquid
line
Shortage
of
refrigerant
due
to
leak
Repair
leak
and
recharge.
Frosted
liquid
line
Restricted
filter
drier
Remove
restriction
or
replace
filter
drier
core.
Compressor
will
not
unload
Burned-out
coil
Replace
coil.
Defective
capacity
control
valve
Replace
valve.
Miswired
solenoid
Rewire
correctly.
Weak,
broken
or
wrong
valve
body
spring
Replace
spring.
Compressor
will
not
load
Miswired
solenoid
Rewire
correctly.
I
Defective
capacity
control
valve
Replace
valve.
Plugged
strainer
(high
side)
Clean
or
replace
strainer.
Stuck
or
damaged
unloader
piston
1
or
piston
rings.
Clean
or
replace
necessary
parts.
15