General Parameters Menu – GENUNIT (continued)
No. Point name Status Unit Displayed text* Description
10 CHIL_S_S dsable / enable - Net.: Cmd Start/Stop Unit start/stop via Network: When the unit is in
Network mode, start/stop command can be forced
11 CHIL_OCC no / yes - Net.: Cmd Occupied Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
12 CAP_T 0 to 100 % Percent Total Capacity Total unit capacity
13 CAPA_T 0 to 100 % Circuit A Total Capacity Total capacity, circuit A
14 CAPB_T 0 to 100 % Circuit B Total Capacity Total capacity, circuit B
15 DEM_LIM 0 to 100 % Active Demand Limit Val Active demand limit value: When the unit is in Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
16 SP - °C Current Setpoint Current setpoint
17 CTRL_PNT -20.0 to 67.2 °C Control Point Control point: Water temperature that the unit must
produce
18 EMSTOP dsable / enable - Emergency Stop Emergency stop: Used to stop the unit regardless of
its active operating type
*Depends on the selected language (English by default).
Temperature Menu – TEMP
No. Point name Status Unit Displayed text* Description
1 EWT - °C Entering Water Temp Evaporator entering water temperature: Used for
capacity control
2 LWT - °C Leaving Water Temp Evaporator leaving water temperature: Used for
capacity control
3 SST_A - °C Saturated Suction Tp A Saturated suction temperature, circuit A
4 SST_B - °C Saturated Suction Tp B Saturated suction temperature, circuit B
5 SUCT_A - °C Gas Suction Temp A Compressor suction temperature, circuit A
6 SUCT_B - °C Gas Suction Temp B Compressor suction temperature, circuit B
7 OAT - °C Outside Air Temperature Outdoor air temperature: Used to determine a number
of control mechanisms
8 COND_EWT - °C Cond Entering Water Temp Condenser entering water temperature
9 COND_LWT - °C Cond Leaving Water Temp Condenser leaving water temperature
10 SCT_A - °C Saturated Condens Tp A Saturated condensing temperature, circuit A
11 SCT_B - °C Saturated Condens Tp B Saturated condensing temperature, circuit B
12 DGT_A - °C Discharge Gas Temp cir A Discharge gas temperature, circuit A
13 DGT_B - °C Discharge Gas Temp cir B Discharge gas temperature, circuit B
14 CHWSTEMP - °C Chilled Water Syst Temp Chilled water system temperature (used for master/
slave assembly control when cooling )
15 HTWSTEMP - °C Heat Water Syst Temp Hot water system temperature (used for master/slave
assembly control when heating)
16 DRY_LWT - °C Dry Cooler Leaving WT Dry cooler – leaving water temperature
17 SPACETMP - °C Optional Space Temp Outdoor air temperature reading
(optional OAT sensor needed)
*Depends on the selected language (English by default).
Pressure Menu – PRESSURE
No. Point name Status Unit Displayed text* Description
1 DP_A - kPa Discharge Pressure A Compressor discharge pressure, circuit A
2 SP_A - kPa Suction Pressure A Compressor suction pressure, circuit A
3 DP_B - kPa Discharge Pressure B Compressor discharge pressure, circuit B
4 SP_B - kPa Suction Pressure B Compressor suction pressure, circuit B
*Depends on the selected language (English by default).