7
3.6 -  Actuators
Electronic Expansion Valve
The electronic expansion valve (EXV) is used to adjust the 
machine. The high degree of accuracy with which the piston 
and suction superheat.
Flow switch
operation and protection of the system is maintained. If the 
Water pumps (optional)
The controller can independently regulate each water heat 
control based on the minimum pump speed setpoint.
temperature difference or the water pressure difference.
Boiler
If there is a unit fault in the heating mode this output authorises 
start-up and shutdown of a boiler. 30WG/30WGA units can 
by the controller in case of heating demand. For 61WG units, 
the boiler is activated when the operating conditions are not 
suitable for thermodynamic heating or the unit is down due 
to a detected failure. See also section 8.10.1.
Electric heaters
Electric heaters are used as a supplementary heating source 
in the heating mode. See also section 8.10.2.
3.7 -  Available connections
Connections available at the user terminal block may vary 
depending on the selected options. The following table 
summarizes connections at the user terminal block.
IMPORTANT: Some contacts can be accessed only when 
the unit operates in Remote mode.
3.7.1 -  Terminal block connections
Description Board Connector Remarks
Remote On/O 
contact
SIOB, 
cir A
+:32/ -:33 Used for the unit on/o 
control (Remote mode)
Remote Heat/
Cool contact
SIOB, 
cir A
+:63/ -:64 Used to set cooling and 
heating when the unit is in 
Remote mode 
Switch-
controlled 
demand limit
SIOB, 
cir A
+:73/ -:74 Used to control demand 
limit
Switch dual 
setpoint
SIOB, 
cir A
+:65/ -:66 Used to select the second 
cooling setpoint
Lock switch SIOB, 
cir A
+:34/ -:35 Used for the customer 
safety loops
Condenser 
3-way valve
SIOB, 
cir A
+:80+/-:80- Used to control the water 
ow on the condenser side
Boiler SIOB, 
cir A
+:69/ -:70 Used to command a boiler
Running SIOB, 
cir A
+:37/-: 38 Used to signal a running 
status (at least one 
compressor start)
Description 
(cont.)
Board 
(cont.)
Connector 
(cont.)
Remarks  
(continued)
Alarm SIOB, 
cir A
+: 30/-: 31 Used to signal an alarm
Domestic hot 
water (DHW)
AUX1 -:310 / 
CH12: 311
Used to control domestic 
hot water production
Domestic hot 
water (DHW) 
priority switch 
AUX1 -:312 / 
+:313
Used to control domestic 
hot water priority
Summer 
switch
AUX1 -:323 / 
+:322
Used to stop the Space 
Heating loop additional 
pump during summer time
Electrical 
Heater Stage 1 
AUX1 341 / 12 Used to control the 
electrical heater stage 1 
Electrical 
Heater Stage 2 
AUX1 342 / 12 Used to control the 
electrical heater stage 2
Electrical 
Heater Stage 3 
AUX1 343 / 12 Used to control the 
electrical heater stage 3
Electrical 
Heater Stage 4 
AUX1 344 / 12 Used to control the 
electrical heater stage 4
Additional 
pump 
command
AUX1 365 / 12 Used to command the 
additional pump in case of 
DHW option
DHW  
diverting valve
AUX1 340 / 12 Used to command the DHW 
loop in case of DHW option
3.7.2 -  Volt-free contact (on/off and cooling/heating)
For units with a boiler, on/off contacts and cooling/heating 
contacts are as follows:
 Cooling Heating
 open closed closed
Cooling/Heating contact open open closed
O:  Unit is stopped
Cooling:  Unit is allowed to start in Cooling
Heating:  Unit is allowed to start in Heating 
3.7.3 -  Volt-free setpoint selection contact
When the unit is under remote control, the volt-free contact 
is used to determine the active setpoint. This dry contact is 
used to switch between setpoints. It is active only when the 
control is in Remote mode. See also section 8.5.1.
Contact
Active setpoint
SP1 SP2 SP3 Auto
SETP_SW1 open close open close
SETP_SW2 open open close close
3.7.4 -  Volt-free demand limit selection contact
One dry contact can be used to limit unit capacity. The limit 
menu (see section 5.6).
100% Limit 1 Limit 2 Limit 3
Demand limit 1 contact open closed open closed
3.7.5 -  Summer switch (HDC option)
For units with HDC option, the summer switch can be used 
to control with the volt-free contact.
Summer switch Summer mode
open not active
closed active