7.1 - Main menu
Icon Displayed text* Description Associated table
General Parameters General Parameters GENUNIT
Temperature Temperature TEMP
Pressure Pressure PRESSURE
Setpoint Setpoint SETPOINT
Inputs Inputs status INPUTS
Outputs Outputs status OUTPUTS
Pump Status Pump Status PUMPSTAT
Heating Device Heating Device HDC_STAT
Runtime Runtime RUNTIME
Free Cooling Status Free Cooling Status FCOOL_ST
Modes Modes MODES
Conguration Conguration menu CONFIG
* Depends on the selected language (English by default).
CAUTION: Since specic units may not include additional features, some tables may contain parameters that cannot be
congured for a given unit.
General Parameters Menu – GENUNIT
No. Point name Status Unit Displayed text* Description
1 CTRL_TYP 0 to 2 - Local=0 Net.=1 Remote=2 Operating mode:
0 = Local
1 = Network
2 = Remote
2 STAT US - - Running Status O, Running, Stopping, Delay, Trip out, Ready,
Override, etc.
3 ALM - - Alarm State Alarm state: Normal, Partial, Shutdown
4 min_left - min Minutes Left for Start Minutes before the unit start-up
5 HEATCOOL - - Heat/Cool Status Heating/cooling status: Heat/Cool
6 HC_SEL 0 to 1 - Heat/Cool Select Heating/cooling selection:
0 = Cooling
1 = Heating
7 SP_SEL 0 to 3 - Setpoint Select Setpoint selection
8 0=Auto 1=Spt1 2=Spt2
3=Spt3
0 = Auto (schedule control)
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
9 SP_OCC no / yes - Setpoint Occupied? Setpoint occupancy status