20
Free Cooling Status Menu – FCOOL_ST (continued)
No. Point name Status Unit Displayed text* Description
6 fc_fanst 0 to 10 - FC Fan Stage Free Cooling / Dry Cooler fan stage
7 fc_fansp 0 to 100 % FC Varifan Speed Free Cooling / Dry Cooler: Fan speed
8 FC_HOUR 0 to 999999 hour FC Operating Hours Free Cooling / Dry cooler: Operating hours
9 FC_FAN1S 0 to 999999 - FC Fan Stage 1 Start FC / Fan stage 1: Number of starts
10 FC_FAN1H 0 to 999999 hour FC Fan Stage 1 Hours FC / Fan stage 1: Operating hours
11 FC_FAN2S 0 to 999999 - FC Fan Stage 2 Start FC / Fan stage 2: Number of starts
12 FC_FAN2H 0 to 999999 hour FC Fan Stage 2 Hours FC / Fan stage 2: Operating hours
13 FC_FAN3S 0 to 999999 - FC Fan Stage 3 Start FC / Fan stage 3: Number of starts
14 FC_FAN3H 0 to 999999 hour FC Fan Stage 3 Hours FC / Fan stage 3: Operating hours
15 FC_FAN4S 0 to 999999 - FC Fan Stage 4 Start FC / Fan stage 4: Number of starts
16 FC_FAN4H 0 to 999999 hour FC Fan Stage 4 Hours FC / Fan stage 4: Operating hours
17 FC_FAN5S 0 to 999999 - FC Fan Stage 5 Start FC / Fan stage 5: Number of starts
18 FC_FAN5H 0 to 999999 hour FC Fan Stage 5 Hours FC / Fan stage 5: Operating hours
19 FC_FAN6S 0 to 999999 - FC Fan Stage 6 Start FC / Fan stage 6: Number of starts
20 FC_FAN6H 0 to 999999 hour FC Fan Stage 6 Hours FC / Fan stage 6: Operating hours
21 FC_FAN7S 0 to 999999 - FC Fan Stage 7 Start FC / Fan stage 7: Number of starts
22 FC_FAN7H 0 to 999999 hour FC Fan Stage 7 Hours FC / Fan stage 7: Operating hours
*Depends on the selected language (English by default).
Modes Menu – MODES
No. Point name Status Unit Displayed text* Description
1 m_delay no / yes - Delay Active Start-up delay in eect
2 m_2ndspt no / yes - Second Setpoint Active Second setpoint in use: The setpoint used during
unoccupied periods
3 m_reset no / yes - Reset Active Setpoint reset active
4 m_limit no / yes - Demand Limit Active Demand limit active
5 m_ramp no / yes - Ramp Loading Active Ramp loading active
6 m_cooler no / yes - Cooler Heater Active Pump enabled for freeze protection
7 m_clpmpp no / yes - Cooler Pump Per. Active Evaporator pump active periodically
8 m_cdpmpp no / yes - Cond. Pump Per. Active Condenser pump active periodically
9 m_night no / yes - Night Low Noise Active Night low noise active
10 m_SM no / yes - System Manager Active System Manager active
11 m_leadla no / yes - Master Slave Active Master/slave mode active
12 m_heater no / yes - Electric Heat Active Electric heating active
13 m_lo_ewt no / yes - Heating Low EWT lockout Heating low EWT lockout
14 m_boiler no / yes - Boiler Active Boiler active status
15 m_ice no / yes - Ice Mode Active Ice mode active (cooling setpoint 3 is used)
16 m_sst_a no / yes - Low Suction Circuit A Low suction, circuit A
17 m_sst_b no / yes - Low Suction Circuit B Low suction, circuit B
18 m_dgt_a no / yes - High DGT Circuit A High DGT, circuit A
19 m_dgt_b no / yes - High DGT Circuit B High DGT, circuit B
20 m_hp_a no / yes - High Pres Override cir A High pressure override, circuit A
21 m_hp_b no / yes - High Pres Override cir B High pressure override, circuit B
22
m_sh_a no / yes - Low SuperHeat circuit A Low superheat, circuit A
23 m_sh_b no / yes - Low SuperHeat circuit B Low superheat, circuit B
24 m_dhw no / yes - Domestic Hot Water Mode Domestic hot water mode status
25 m_summer no / yes - Summer Mode Active Summer mode status
*Depends on the selected language (English by default).