Pump Conguration Menu – PUMPCONF (continued)
No. Point name Status Default Unit Displayed text* Description
5 2 = Two Pumps Auto 2 = Two Pumps Auto (units with two pumps)
6 3 = Pump#1 Manual 3 = Pump#1 Manual
7 4 = Pump#2 Manual 4 = Pump#2 Manual
8 clpmpdel 24 to 3000 48 hour Pump Auto Rotation Delay Pump auto rotation delay (units with two
pumps = auto control)
9 clpmpper no / yes no - Cool Pump Anti-Sticking Evaporator pump anti-sticking protection
10 clpmpsby no / yes no - Cool Pump Stopped in Sby Not applicable (please ignore this parameter)
11 clpmploc no / yes no - Flow Checked if Pump O Water ow is checked when the pump is o
12 CONDENSER PUMP CONDENSER PUMP
13 cdpmpseq 0 to 4 0 - Condenser Pumps Sequence Condenser pump sequence
14 0 = No Pump 0 = No Pump
15 1 = One Pump Only 1 = One Pump Only
16 2 = Two Pumps Auto 2 = Two Pumps Auto (units with two pumps)
17 3 = Pump#1 Manual 3 = Pump#1 Manual
18 4 = Pump#2 Manual 4 = Pump#2 Manual
19 cdpmpdel 24 to 3000 48 hour Pump Auto Rotation Delay Pump Auto Rotation Delay (units with two
pumps = auto control)
20 cdpmpper no / yes no - Cond Pump Anti-Sticking Condenser pump anti-sticking protection
21 cdpmpsby no / yes no - Cond Pump Stopped in Sby Not applicable (please ignore this parameter)
22 cdpmploc no / yes no - Flow Checked if Pump O Water ow is checked when the pump is o
23 ol_pump no / yes no - Open loop pump Control Open loop pump control
*Depends on the selected language (English by default).
Heat/Cool Cong Menu – HCCONFIG
No. Point name Status Default Unit Displayed text* Description
1 cr_sel 0 to 3 0 - Cooling Reset Select Cooling reset selection
2 hr_sel 0 to 3 0 - Heating Reset Select Heating reset selection
3 0=none, 1=OAT, 0 = None, 1 = OAT,
4 2=delta T, 3=4-20mA 2 = Delta T, 3 = 4-20 mA control
5 boil_on no / yes no Boiler Manual Command Boiler manual command:
No = boiler control based on OAT control logic
(see boil_th below)
Yes = boiler control enabled if OAT sensor is
NOT present or the sensor fails
6 boil_th -15 to 15 -10 °C Boiler OAT Threshold Boiler OAT threshold
7 ehs_th -4.90 to 21.42 5.2 °C Elec Stage OAT Threshold Electric heating stage, OAT threshold
8 both_sel no / yes no - HSM Both Command Select HSM both command selection
9 ehs_back no / yes no - 1 Elec Stage for Backup One electric heating stage used for back-up
10 ehs_pull 0 to 60 0 min Electrical pulldown time Electrical pull-down time
*Depends on the selected language (English by default).
HDC Conguration Menu – HDC_CONF
No. Point name Status Default Unit Displayed text* Description
1 adpmpper no / yes no - Add. Pump Anti-Sticking Additional pump anti-sticking protection
2 summ_oat 15.0 to 30.0 20.0 °C Summer OAT threshold This threshold denes when Summer mode
can be started
3 summ_on 0 to 12 5 hour Summer OAT start delay Summer mode is activated if OAT is above
OAT Threshold [sum_oat] for at least the
sum_on delay
4 summ_o 0 to 12 5 hour Summer OAT stop delay Summer mode is reset when OAT goes below
OAT Threshold [sum_oat] minus 2K for at least
the sum_o delay