17
TEMP – Temperatures
No. Status Unit
1 - °C/°F Cooler Entering Fluid Evaporator entering water temperature
2 - °C/°F Cooler Leaving Fluid Evaporator leaving water temperature
3 - °C/°F Outdoor Air Temperature Outdoor air temperature
4 - °C/°F Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
5 - °C/°F Saturated Suction Temp A Saturated suction temperature, circuit A
6 - °C/°F Saturated Liquid Temp A Saturated liquid temperature, circuit A
7 - °C/°F Compressor Suction Tmp A Compressor suction temperature, circuit A
8 - °C/°F Discharge Gas Temp cir A Discharge gas temperature, circuit A
9 - °C/°F Motor Temperature cir A Motor temperature, circuit A
10 - °C/°F EXV Eco. Tmp cir A EXV economizer temperature, circuit A
11 - °C/°F Liquid Temperature A Liquid temperature, circuit A
12 - °C/°F Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
13 - °C/°F Saturated Suction Temp B Saturated suction temperature, circuit B
14 - °C/°F Saturated Liquid Temp B Saturated liquid temperature, circuit B
15 - °C/°F Compressor Suction Tmp B Compressor suction temperature, circuit B
16 - °C/°F Discharge Gas Temp cir B Discharge gas temperature, circuit B
17 - °C/°F Motor Temperature cir B Motor temperature, circuit B
18 - °C/°F EXV Eco. Tmp cir B EXV economizer temperature, circuit B
19 - °C/°F Liquid Temperature B Liquid temperature, circuit B
20 - °C/°F Optional Space Temp Optional space temperature
21 - °C/°F CHWS Temperature Master/slave common water temperature
22 - °C/°F Cooler Heater Temp Evaporator heater temperature
*Depends on the selected language (English by default).
PRESSURE – Pressures
No. Status Unit
1 - kPa/PSI Discharge Pressure A Discharge pressure, circuit A
2 - kPa/PSI Main Suction Pressure A Main suction pressure, circuit A
3 - kPa/PSI Oil Pressure A Oil pressure, circuit A
4 - kPa/PSI Oil Pressure DierenceA Oil pressure dierence, circuit A
5 - kPa/PSI Economizer Pressure A Economizer pressure, circuit A
6 - kPa/PSI Liquid Pressure A Liquid pressure, circuit A
7 - kPa/PSI Discharge Pressure B Discharge pressure, circuit B
8 - kPa/PSI Main Suction Pressure B Main suction pressure, circuit B
9 - kPa/PSI Oil Pressure B Oil pressure, circuit B
10 - kPa/PSI Oil Pressure DierenceB Oil pressure dierence, circuit B
11 - kPa/PSI Economizer Pressure B Economizer pressure, circuit B
12 - kPa/PSI Liquid Pressure B Liquid pressure, circuit B
13 - kPa/PSI Entering water pressure Entering water pressure (before evaporator)
14 - kPa/PSI Leaving water pressure Leaving water pressure (after evaporator)
15 - kPa/PSI Water pressure 3 Water pressure (Not applicable)
16 - kPa/PSI Water pressure 4 Water pressure (Not applicable)
*Depends on the selected language (English by default).
INPUTS – Inputs status
No. Status Unit
1 open/close - Remote On/O Switch Remote On/O switch
2 open/close - Remote Setpoint Switch Remote setpoint switch
3 open/close - Limit Switch 1 Demand limit switch 1
4 open/close - Limit Switch 2 Demand limit switch 2
5 open/close - Oil Level Input A Oil level input, circuit A
6 open/close - Oil Level Input B Oil level input, circuit B
7 - mA Reset/Setpnt4-20mA Sgnl 4-20 mA signal, setpoint reset
8 - mA Limit 4-20mA Signal 4-20 mA signal, capacity limitation
9 - V Leakage detector 1 val Leakage detection input 1
10 - V Leakage detector 2 val Leakage detection input 2
11 open/close - Customer Interlock Customer interlock status
12 open/close - Ice Done Storage Switch Ice storage end switch
13 open/close - Occupied Override Switch Occupied override switch
14 open/close - Remote Reclaim switch Remote reclaim switch
15 open/close - Electrical box Interlock Electrical box interlock
16 open/close - Cooler Heater Detector Evaporator heater input
17 no/yes - BACnet dongle BACnet dongle
*Depends on the selected language (English by default).