AIRSOURCEBUSANDELEMENTNUMBER-- TheAir
SourceBusandElementNumberconfigurationsdefinethe
addressoftheairsourceprovidingconditionedairtothezones
controlledbythelinkagecoordinatol:If theaddressisleftat
zero,thelinkagecoordinatorwilllookforaprimal"/airsensor
todeterminetheequipmentmode.If noprimal"/airsensoris
installed,or thesensorfails,theLinkageCoordinatorwill
defaulttheairsourcemodetoCooling.
AirSource
BusNumber: Range 0to239
DefaultValue 0
AirSoume
ElementNumber:Range 0to239
DefaultValue 0
Table 7 -- Damper Service Configuration Table
DESCRIPTION VALUE UNITS NAME
Cool Minimum Pos 0 % CMINPOS
Cool Maximum Pos 100 % CMAXPOS
Reheat Minimum Pos 0 % REMINPOS
Heat Minimum Pos 0 % HMINPOS
Heat Maximum Pos 100 % HM_POS
Ventilation Pos 30 % VENTPOS
Table 8 -- Holiday Configuration Table
DESCRIPTION VALUE UNITS NAME
Start Month 1 MONTH
Start Day 1 DAY
Duration 0 DURATION
Table 9 -- Linkage Configuration Table
DESCRIPTION VALUE UNITS NAME
Zone Linkage
Linkage Master Zone No MAST_ENA
Number of Zones 1 NUM_ZONE
Air Source Bus # 0 AS_BUS
Air Source Element # 0 AS_ELEM
System Bypass Exists Yes SYS_BP
SAT Mode Verification No SAT_CHCK
Supply Air Location 0 SAT_LOC
0 = Airsource
1 = Local PAT
2 = Bypass
CCN-LINKAGE DATA
CCN Variable Name CCNVAR
CCN Func Config 0 CCNFUNC
0 = None
1 = Average
2 = Low
3 = High
Data Transfer Rate 10 rain DATARATE
CCN Output Point CCNOUTP
Destination Bus # 0 DESTBUSN
Destination Element # 0 DESTELEN
TEMP SENSOR GROUPING
Sensor Mode 1 BRD_RECV
1 = Local Sensor
2 = Broadcast
3 = Listen
Listen Sensor Config 1 SENSCFG
1 = SPT
2 = SPT & Offset
Broadcasting Element # 1 BRDDEVID
34