7GB-13
6. REFRIGERANT PIPING CONNECTION
6.1 Safety Precautions707
 WARNING
• All field piping must be completed by a 
licensed technician and must comply 
with the local and national regulations. 
• 
When the air conditioner is installed in a 
small room, measures must be taken to 
prevent the refrigerant concentration in 
the room from exceeding the safety limit 
in the event of refrigerant leakage. If the 
refrigerant leaks and its concentration 
exceeds its proper limit, hazards due to 
lack of oxygen may result.     
•  When installing the refrigeration system, 
ensure that air, dust, moisture or foreign 
substances do not enter the refrigerant 
circuit. Contamination in the system may 
cause poor operating capacity, high 
pressure in the refrigeration cycle, 
explosion or injury.     
• 
Ventilate the area immediately if there is 
refrigerant leakage during the 
installation. Leaked refrigerant gas is 
both toxic and flammable. Ensure there 
is no refrigerant leakage after 
completing the installation work.    
Refrigerant Piping Connection Instructions
 CAUTION
•  The branching pipe must be installed 
horizontally. An angle of more than 10° 
may cause malfunction. 
•  DO NOT install the connecting pipe 
until both indoor and outdoor units have 
been installed. 
 
•  Insulate both the gas and liquid piping to 
prevent water leakage. 
Step1: Cut pipes
When preparing refrigerant pipes, take extra 
care to cut and flare them properly. This will 
ensure efficient operation and minimize the 
need for future maintenance.   
1. Measure the distance between the 
indoor and outdoor units. 
2. Using a pipe cutter, cut the pipe a little 
longer than the measured distance. 
 CAUTION
DO NOT deform pipe while cutting. Be 
extra careful not to damage, dent, or 
deform the pipe while cutting. This will 
drastically reduce the heating efficiency 
of the unit.  
 
1. Make sure that the pipe is cut at a perfect 
90° angle. Refer to Fig. 6.1 for examples of 
bad cuts 
Oblique
Rough
Warped
90°
Fig. 6.1
Step 2: Remove burrs.
Burrs can affect the air-tight seal of 
refrigerant piping connection. They must be 
completely removed. 
1. Hold the pipe at a downward angle to 
prevent burrs from falling into the pipe. 
2. Using a reamer or deburring tool, 
remove all burrs from the cut section 
of the pipe. 
Pipe
Reamer
Point down
Fig. 6.2
Step 3: Flare pipe ends
Proper flaring is essential to achieve an 
airtight seal.
1.
After removing burrs from cut pipe, seal 
the ends with PVC tape to prevent 
foreign materials from entering the pipe. 
2.
Sheath the pipe with insulating material.
3.
Place flare nuts on both ends of pipe. 
Make sure they are facing in the right 
direction, because you can’t put them 
on or change their direction after flaring. 
See Fig. 6.3   
Flare nut
Copper pipe
Fig. 6.3
NOTE
    For R32 refrigerant models, the pipe connection
    points must be placed outside of room.