APPENDIX A -- USER INTERFACE MENUS (CON’T)
Configuration Menus (con’t)
BACview MENU POINT NAME
BACnet
OBJECT
RANGE DEFAULT FIELD ASSISTANT MENU
HOME Select function below Properties/Equipment
SERVICE
SERVICE CONFIGURATION
Service Configuration
Unit Type unit_type 1=Heat/Cool
2=HP O/B Ctrl
3=HP Y1/W1
Ctrl
Heat/Cool (TC and
HC models)
HP Y1/W1 Ctrl
(TCQ an d HCQ
models)
Compressor Stages comp_stages One stage/ Two
Stage
One Stage (sizes
04---07, a nd
A 0 8 --- A 1 2 )
Two Stages (sizes
08---30)
Economizer Exists econ_exist No/Yes No ( No FIOP)
Ye s ( FI OP )
Reversing Valve Type re v_vlv_type Ooutputtype/B
output type
Ooutputtype
Heat Type heat_type Electric/Gas Gas (48 Series
Units)
Electric (50 Series
Units)
Number of Heat Stages heat_stages 1/2/0(no
heat)
0 (50 series cool-
ing only units)
1(AllTCQsand
HCQs, L ow Nox
units, single phase
gas units,
TC04 ---09 low an d
TC05 ---07 med
heat 3 phase gas
units)
2(TC04and
08---09 med,
TC05 ---09 high
heat 3 phase gas
units, HC04---09 3
phase gas units
and All 12---30 gas
units)
Continuous Occupied Exhaust occ_exh No/Yes No
Indoor CO2 Sensor Value @
Min mA
iaq_ref_lo_ppm 0---9999ppm 0
Indoor CO2 Sensor Value @
Max mA
iaq_ref_hi_ppm 0 ---9999ppm 2000
Outdoor CO2 Sensor Value @
Min mA
oaq_ref_lo_ppm 0 ---9999ppm 0
Outdoor CO2 Sensor Value @
Max mA
oaq_ref_hi_ppm 0 ---9999ppm 2000
(Field Assistant Only)
System Space Temperature system_spt
System Cooling Demand Level cool_de-
mand_level
0 --- 3 0
System Heating Demand Level heat_de-
mand_level
0 --- 3 0
System Outdoor Air Temperat-
ure
system_oat
TEST
SERVICE TE ST
Service Test test_enable Disable/Enable Disable
Fan T est fan_test Disable/Enable Disable
Compressor 1 Test comp1_test Disable/Enable Disable
Compressor 2 Test comp2_test Disable/Enable Disable
Heat 1 Test heat1_test Disable/Enable Disable
Heat 2 Test heat2_test Disable/Enable Disable
Reversing Valve Test rev_vlv_test Disable/Enable Disable
Dehumidification Test dehum_test Disable/Enable Disable
Power Exhaust T est pexh_test Disable/Enable Disable
Economizer Test econ_ test 0 --- 1 0 0 % O p e n 0
Analog Output 2 T est ao2_test 0 --- 1 0 0 % 0