EasyManua.ls Logo

Carrier 48/50HC04---14 - Page 32

Carrier 48/50HC04---14
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
APPENDIX A -- USER INTERFACE MENUS (CON’T)
Configuration Menus (con’t)
BACview MENU POINT NAME
BACnet
OBJECT
RANGE DEFAULT FIELD ASSISTANT MENU
HOME Select function below Properties/Equipment
INPUT
INPUT CONFIGURATION
Unit Configuration
Input 1 Function ai1_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
No Sensor
Input 2 Function ai2_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
1(NoFIOP)
2(FIOP)
Input 3 Function di3_function 1=No Function
2=Compressor
Safety
3=Fan Status
4=Filter Status
5=Remote Oc-
cupancy
6=Door Contact
Compressor Safety
Input 3 Switch Configuration di3_type N/O
N/C
N/O
Input 5 Function di5_function 1=No Function
2=Fire Shut-
down
3=Fan Status
4=Filter Status
5=Remote Oc-
cupancy
6=Door Contact
Fire Shutdown
Input 5 Switch Configuration di5_type N/O
N/C
N/O
Input 8 Function di8_function 1=No Function
2=Enthalpy
Switch
3=Fan Status
4=Filter Status
5=Remote Oc-
cupancy
6=Door Contact
1(NoFIOP)
2(FIOP)
Input 8 Switch Configuration di8_type N/O
N/C
N/O
Input 9 Function di9_function 1=No Function
2=Humidistat
3=Fan Status
4=Filter Status
5=Remote Oc-
cupancy
6=Door Contact
Humidistat
Input 9 Switch Configuration di9_type N/O
N/C
N/O
Space sensor type spt_type 1=T55
2=T56 (use for
T59)
3=SPT Sensor
T55
T5x Override Duration ovr_dur 0---24 hours 1

Related product manuals