11 - TECHNICAL SPECIFICATIONS
11.2.2 - Electric heater
Operates in two on/o󰀨 stages or with TRIAC (modulating).
The latter allows the power of the electric heater to be varied to ensure it is as close as possible to the required heating capacity. The
connection is carried out in the factory. The electric heater is equipped with two safety thermostats, one with automatic reset and the
other with manual reset.
CHILLED WATER
W40 W53 W78 W100 W115
Power (kW) 12 18 24 33,6 33,6
Power (kW)
stage 1 6 12 12 16,8 16,8
stage 2 6 6 12 16,8 16,8
Number of heaters
stage 1 3 x 2 kW 3 x 4 kW 3 x 4 kW 3 x 5.6 kW 3 x 5.6 kW
stage 2 3 x 2 kW 3 x 2 kW 3 x 4 kW 3 x 5.6 kW 3 x 5.6 kW
Total current (A) 17,3 26 34,7 48,6 48,6
11.2.3 - Humidier
Functions only with municipal water, and not with demineralised or softened water.
The humidier with immersed electrodes has a card mounted inside the box to relay all information relating to the humidier directly 
to the CCU CONTROLLER. It adapts, within the allowable operating limits, to the physical and chemical properties of the water used.
Voltage is applied to the immersed electrodes, and an electrical current passes between them, heating the water to boiling point. The
water acts as an electrical resistor, ensuring continuity between the electrodes with a minimum of dissolved salts.
(The water must have a conductivity of between 350 µS/cm and 125 µS/cm.)
W40 to W115
Control voltage 24 V
Input power
control circuit
Without 9 V A valve; with 35 V A valve
High power circuit voltage 3-PH/400 V
Power circuit current (A) 8.7 A
Protection rating 16 A
Max. power 6 kW
Factory power setting W40 to W1006: 6 kW
Factory steam ow rate setting
W40 to W100 8 kg/h: (100%)
W115: 8 kg/h: (100%)
Steam ow rate 5 to 8 kg/h
Water supply pressure 1 to 8 bar
Max. water supply ow rate 0.6 L/min
Conductivity of supply water 350 to 1250 µs/cm
Hydrogen ion activity (PH) 7 to 8 ph
Drain water ow rate  4 L/min
Water supply ø G ¾'' male
Drain ø 32 mm
Hardness of TH supply water 100 to 400 mg/l Ca CO
³
Connection:
it is supplied with a exible water supply tube at the back of the unit.
To drain it, carry out siphoning.
Warning: the water temperature can reach 100°C.