11 - TECHNICAL SPECIFICATIONS
11.2.4 - Condensate drain pump:
This option is only available if the humidier option has not been requested.
Characteristics:
- Power supply: 230V-50Hz-90W
- Max. ow rate: 500 l/h
- Max. discharge height: 5.4 m
- Built-in check valve
Condensate discharge
with check valve
Table of actual ow rates for pump SI 1805
The pressure drops dened in this table are 
calculated using a 10 mm diameter exible 
connection
Discharge
height
Total pipe length
5 m (l/h) 10 m (l/h) 20 m (l/h) 30 m (l/h)
1 m 460 380 280 200
2 m 390 320 240 180
3 m 300 250 190 150
4 m 200 180 130 100
5 m 90 80 60 50
Connect a exible connection with an int. Ø 10 mm (3/8") (not supplied by CARRIER) to the pump discharge.
For OVER models (3 and 5), if using a spreader beam and slings, the PVC tube will not be directly connected to the pump, for handling
reasons. It must therefore be angled in the right direction and xed to the clamp, as shown below.
Clamp
PVC tube
Elbow