Parameters of “Unit On/O
13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Unit Status” (...continuation)
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
P04 NUM_WO_DIG_3 Work order number of the unit (digit 3) 0 0 9 ---
Analog. R
187
P04 NUM_WO_DIG_4 Work order number of the unit (digit 4) 0 0 9 ---
Analog. R
188
P04 NUM_WO_DIG_5 Work order number of the unit (digit 5) 0 0 9 ---
Analog. R
189
P04 NUM_WO_DIG_6 Work order number of the unit (digit 6) 0 0 9 ---
Analog. R
190
P04 NUM_WO_DIG_7 Work order number of the unit (digit 7) 0 0 9 ---
Analog. R
191
P04 NUM_WO_DIG_8 Work order number of the unit (digit 8) 0 0 9 ---
Analog. R
192
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
PM01 SYS_ON Selection of the unit ON/OFF by keyboard or remote: 0: Switch-o󰀨 (O󰀨 ) # 1: Switch-on (On) 0 0 1 --- Digital R/W 65
PM01z SYS_ON_T11 Selection of the zone 1 ON/OFF by keyboard or remote: 0: Switch-o󰀨 (O󰀨 ) # 1: Switch-on (On) 0 0 1 --- Digital
R/W
364
PM01z SYS_ON_T12 Selection of the zone 2 ON/OFF by keyboard or remote: 0: Switch-o󰀨 (O󰀨 ) # 1: Switch-on (On) 0 0 1 --- Digital
R/W
365
PM01z SYS_ON_T13 Selection of the zone 3 ON/OFF by keyboard or remote: 0: Switch-o󰀨 (O󰀨 ) # 1: Switch-on (On) 0 0 1 --- Digital
R/W
366
PM01z SYS_ON_T14 Selection of the zone 4 ON/OFF by keyboard or remote: 0: Switch-o󰀨 (O󰀨 ) # 1: Switch-on (On) 0 0 1 --- Digital
R/W
367
Parameters of “Setpoint”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
S01zn SET_POINT_TEMP_FRIO_T11
Temperature setpoint in COOLING mode (summer) in the terminal of zone
1 (zoning of the air ow)
26.0 0.0 50.0 °C Analog. R/W 283
S01zn SET_POINT_TEMP_CALOR_T11
Temperature setpoint in HEATING mode (winter) in the terminal of zone 1
(zoning of the air ow)
21.0 0.0 50.0 °C Analog. R/W 284
S02zn SET_POINT_TEMP_FRIO_T12
Temperature setpoint in COOLING mode (summer) in the terminal of zone
2 (zoning of the air ow)
26.0 0.0 50.0 °C Analog. R/W 285
S02zn SET_POINT_TEMP_CALOR_T12
Temperature setpoint in HEATING mode (winter) in the terminal of zone 2
(zoning of the air ow)
21.0 0.0 50.0 °C Analog. R/W 286
S03zn SET_POINT_TEMP_FRIO_T13
Temperature setpoint in COOLING mode (summer) in the terminal of zone
3 (zoning of the air ow)
26.0 0.0 50.0 °C Analog. R/W 287
S03zn SET_POINT_TEMP_CALOR_T13
Temperature setpoint in HEATING mode (winter) in the terminal of zone 3
(zoning of the air ow)
21.0 0.0 50.0 °C Analog. R/W 288
S04zn SET_POINT_TEMP_FRIO_T14
Temperature setpoint in COOLING mode (summer) in the terminal of zone
4 (zoning of the air ow)
26.0 0.0 50.0 °C Analog. R/W 289
S04zn SET_POINT_TEMP_CALOR_T14
Temperature setpoint in HEATING mode (winter) in the terminal of zone 4
(zoning of the air ow)
21.0 0.0 50.0 °C Analog. R/W 290
S01 SET_POINT_TEMP_FRIO Temperature setpoint in COOLING mode (summer) 26.0 0.0 50.0 °C Analog. R/W 15
S01 SET_POINT_TEMP_CALOR Temperature setpoint in HEATING mode (winter) 21.0 0.0 50.0 °C Analog. R/W 16
S02 SET_POINT_HUM Indoor humidity setpoint 50.0 0.0 100.0 %rH Analog. R/W 18
S02
HAB_SONDA_HUM_INT_
VIRTUAL
Enabling the indoor humidity probe in the SHRD shared network 0 0: no
1:
yes
--- Digital R
S03 SET_COMPRESOR_EN_FRIO
Calculation of setpoints: Setpoint in COOLING mode (summer) + Dead
Zone / 2
0.0 0.0 99.9 °C Analog. R
S03 SET_COMPRESOR_EN_CALOR Calculation of setpoints: Setpoint In HEATING mode (winter) + Dead Zone / 2 0.0 0.0 99.9 °C Analog. R
S03 SET_TEMP_COMPRESOR Current selection of the setpoint 0.0 0.0 99.9 °C Analog. R
S03 SET_RES_EN_FRIO Calculation of setpoints: Setpoint of the electrical heaters in COOLING mode 0.0 0.0 99.9 °C Analog. R
S03 SET_RES_EN_CALOR Calculation of setpoints: Setpoint of the electrical heaters in HEATING mode 0.0 0.0 99.9 °C Analog. R
S03 SET_TEMP_RES Current selection of setpoint for electrical heaters 0.0 0.0 99.9 °C Analog. R
S03 SET_VLV_CALOR_EN_FRIO Calculation of setpoints: Setpoint of the hot water coil in COOLING mode 0.0 0.0 99.9 °C Analog. R/W
S03 SET_VLV_CALOR_EN_CALOR Calculation of setpoints: Setpoint of the hot water coil in HEATING mode 0.0 0.0 99.9 °C Analog. R/W
S03 SET_VLV_CALOR Current selection of setpoint for the hot water coil 0.0 0.0 99.9 °C Analog. R/W
S03 SET_FCOOL_VER Calculation of setpoints: free-cooling in summer 00.0 -99.9 99.9 --- Integer R
S03 SET_FCOOL_INV Calculation of setpoints: free-cooling in winter 00.0 -99.9 99.9 --- Integer R
S03 SET_FHEAT Calculation of setpoints: free-heating 00.0 -99.9 99.9 --- Integer R
S04 SET_IMPULSION_FRIO_CAL Supply setpoint calculated in COOLING mode 7.0 0.0 30.0 °C Analog. R 122
S04 SET_IMPULSION_CALOR_CAL Supply setpoint calculated in HEATING mode 45.0 0.0 55.0 °C Analog. R 121