33
Parameters of “Summer/Winter”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
FC01 SEL_FRIO_CALOR
Procedures for the selection of the COOLING/HEATING mode:
0: by keyboard
1: remote (by digital input)
2: auto
3: only ventilation
4: ventilation 100% fresh air
5: SHRD shared network
2
05
--- Integer R/W 59
FC01 MODO_FRIO_CALOR_AUTO
COOLING/HEATING selection in AUTO:
0: by indoor temperature; 1: by outdoor temperature
1
01
--- Digital R/W 232
FC01 CALOR_FRIO_PANEL
COOLING/HEATING selection by keyboard:
0: HEATING (winter); 1: COOLING (summer)
1 0 1 --- Digital R/W 66
FC01 SET_TEMP_EXT_CAMBIO_FRIO Outdoor temperature setpoint for change to COOLING mode (in AUTO mode) 22.0 99.9 99.9 °C Analog. R/W 223
FC01 SET_TEMP_EXT_CAMBIO_CALOR Outdoor temperature setpoint for change to HEATING mode (in AUTO mode) 20.0 99.9 99.9 °C Analog. R/W 222
FC01
PGD1_bloqueado_SEL_FRIO_
CALOR
Enabling of the blocking of summer / winter selection in the Graphic terminal
(so that the nal user cannot change it)
0 0 1 --- Digital R/W 240
FC01 ON_VENT_100_AE_REMOTO
Enabling of the VENTILATION mode with 100% fresh air remotely (analog
input U2 of the c.pCOe expansion card with address 8)
0 0 1 --- Digital R
13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of “Clock/Scheduler”
Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W
Add.
BMS
PH01 TIPO_RELOJ Type of clock (No, Actual) 1 0 2 --- Integer R/W 57
PH01 NEW_HOUR Setting the clock: new hour 0 0 23 h Integer R/W 119
PH01 NEW_MINUTE Setting the clock: new minute 0 0 59 min Integer R/W 120
PH01 NEW_DAY Setting the clock: new day 0 0 31 day Integer R/W 121
PH01 NEW_MONTH Setting the clock: new month 0 0 12 month Integer R/W 122
PH01 NEW_YEAR Setting the clock: new year 0 0 99 year Integer R/W 123
PH01 DIA_SEMANA Day of the week 0 0 0 day Integer R/W 52
PH01 NEW_DATE_MSK Con rm time change 0 0 1 --- Digital R/W
PH02 TZ_Idx
Index used to change the time zone (management change from
winter to summer and vice versa automatically)
52 1
TZ_
IdxMax
--- Integer R
PH03 TIPO_PROG_HORARIA
Type of start-up:
0 = ON/OFF schedule
1 = Schedule only setpoint change
2 = ON/OFF schedule with limit SET of ON
3 = Forced
4 = 3 setpoints schedule + OFF of unit
3 0 4 --- Integer R/W 71
PH03 ARR_FORZADO Forced start-up 0 0 1 --- Digital R/W 120
PH03 TIME_ARR_FORZADO On time with forced start-up 2 1 999 h Integer R/W 73
PH03
HAB_BLOQ_COMP_ON_FASE_LIM_
FRIO
Disable the compressors in summer with “ON/OFF schedule with
limit SET of ON” (nocturnal freecooling)
0 0 1 --- Digital R/W 72
PH03
HAB_BLOQ_RENOVACION_ON_FASE_
LIM
Disable the outdoor air renewal with “ON/OFF schedule with limit
SET of ON” (nocturnal operation)
0 0 1 --- Digital R/W 73
PH04 H_ARR_1A Start-up hour of slot 1- program 1 6 0 23 h Integer R/W 74
PH04 M_ARR_1A Start-up minute of slot 1-program 1 30 0 59 min Integer R/W 75
PH04 H_PAR_1A Stop hour of slot 1 - program 1 11 0 23 h Integer R/W 76
PH04 M_PAR_1A Stop minute of slot 1 - program 1 0 0 59 min Integer R/W 77
PH04 H_ARR_1B Start-up hour of slot 2 - program 1 11 0 23 h Integer R/W 78
PH04 M_ARR_1B Start-up minute of slot 2 - program 1 30 0 59 min Integer R/W 79
PH04 H_PAR_1B Stop hour of slot 2 - program 1 13 0 23 h Integer R/W 80
PH04 M_PAR_1B Stop minute of slot 2 - program 1 30 0 59 min Integer R/W 81
PH04 H_ARR_1C Start-up hour of slot 3 - program 1 15 0 23 h Integer R/W 82
PH04 M_ARR_1C Start-up minute of slot 3 - program 1 0 0 59 min Integer R/W 83
PH04 H_PAR_1C Stop hour of slot 3 - program 1 19 0 23 h Integer R/W 84
PH04 M_PAR_1C Stop minute of slot 3 - program 1 0 0 59 min Integer R/W 85
PH05 H_ARR_2A Start-up hour of slot1 - program 2 8 0 23 h Integer R/W 86
PH05 M_ARR_2A Start-up minute of slot 1 - program 2 0 0 59 min Integer R/W 87
PH05 H_PAR_2A Stop hour of slot 1 - program 2 14 0 23 h Integer R/W 88
PH05 M_PAR_2A Stop minute of slot 1 - program 2 0 0 59 min Integer R/W 89
PH05 H_ARR_2B Start-up hour of slot 2 - program 2 17 0 23 h Integer R/W 90
PH05 M_ARR_2B Start-up minute of slot 2 - program 2 0 0 59 min Integer R/W 91
PH05 H_PAR_2B Stop hour of slot 2 - program 2 20 0 23 h Integer R/W 92
PH05 M_PAR_2B Stop minute of slot 2 - program 2 30 0 59 min Integer R/W 93
PH05 H_ARR_2C Start-up hour of slot 3 - program 2 0 0 23 h Integer R/W 94
PH05 M_ARR_2C Start-up minute of slot 3 - program 2 0 0 59 min Integer R/W 95
PH05 H_PAR_2C Stop hour of slot 3 - program 2 0 0 23 h Integer R/W 96
HCCONFIG
B
SCHEDULE
L