58TN0B/58TN1B: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
Caution!! For the following furnace and vent orientations, use the minimum vertical heights as specified in Table 12.
For all other orientations, follow exclusively the National Fuel Gas Code.
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFPA 54/ANSI Z223.
A03208
Fig. 32 – Upflow Application - Vent Elbow Up
A03210
Fig. 33 – Downflow Application - Vent Elbow Up then Left
A03209
Fig. 34 – Upflow Application - Vent Elbow Right
A03211
Fig. 35 – Downflow Application - Vent Elbow Up
Table 12 – Recommended Minimum Vent Height Per Furnace and Vent Orientation
FURNACE
ORIENTATION
VENT ORIENTATION
FURNACE INPUT
(BTUH/HR)
MIN. VENT
DIAMETER
IN. (mm)
*
*. 4-in. (102 mm) inside casing or vent guard
MIN. VERTICAL VENT
HEIGHT
FT. (M)
†
†. Including 4 in. (102 mm) vent section(s)
Downflow Vent elbow left, then up Fig. 37 132,000 & 110,000 5 (127) 12 (3.6)
Horizontal Left Vent elbow right, then up Fig. 40 132,000 5 (127) 7 (2.1)
Horizontal Left Vent Elbow up Fig. 41 132,000 5 (127) 7 (2.1)
Downflow Vent elbow up then left Fig. 33 110,000 5 (127) 10 (3.0)
Downflow Vent elbow up, then right Fig. 38 110,000 5 (127) 10 (3.0)
SEE NOTES: 1,2,4,7,8,9
on the page following
these figures
SEE NOTES:1,2,3,4,5,7,8,9
on the page following
these figures
SEE NOTES: 1,2,3,4,7,8,9
on the pages following
these figures
SEE NOTES: 1,2,4,5,7,8,9
on the page following
these figures