EasyManua.ls Logo

Carrier 59SC2A - Cleaning Heat Exchangers

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9,
Turn
gas
on
at
electric
switch
on
gas
valve
and
at
external
shut-off
or
meter
10.
Turn
power
on
at
external
disconnect,
fuse
or
circuit
break-
er.
11.
Run
the
furnace
through
two
complete
heating
cycles
to
check
for
proper
operation
12.
Install
control
door
when
complete.
Checking
Heat
Pad
Operation
(If
Applicable)
In
applications
where
the
ambient
temperature
around
the
furnace
is
32°F
or
lower,
freeze
protection
measures
are
required.
If
this
application
is
where
heat tape
has
been
applied,
check
to
ensure
it
will
operate
when
low
temperatures
are
present.
NOTE:
The
Heat
Pad,
when
used,
should
be
wrapped
around
the
condensate
drain
trap.
There
is
no
need
to
use
heat tape
within
the
furnace
casing.
Most
heat
tapes
are
temperature
activated,
and
it
is
not
practical
to
verify
the
actual
heating
of
the
tape.
Check
the
following:
1.
Check
for
signs
of
physical
damage
to
heat tape
such
as
nicks,
cuts,
abrasions,
gnawing
by
animals,
etc.
2.
Check
for
discolored
heat tape
insulation.
If
any
damage
or
discolored
insulation
is
evident,
replace
heat
tape.
3.
Check
that
heat tape
power
supply
circuit
is
on.
Cleaning
Heat
Exchangers
The
following
items
must
be
performed
by
a
qualified
service
technician.
Primary
Heat
Exchangers
If
the
heat
exchangers
get
an
accumulation
of
light
dirt
or
dust on
the
inside,
they
may
be
cleaned
by
the
following
procedure:
NOTE:
If
the
heat
exchangers
get
a
heavy
accumulation
of
soot
and
carbon,
both
the
primary
and
secondary
heat
exchangers
should
be
replaced
rather
than
trying
to
clean
them
thoroughly
due
to
their
intricate
design.
A
build-up
of
soot
and
carbon
indicates
that
a
problem
exists
which
needs
to
be
corrected,
such
as
improper
adjustment
of
manifold
pressure,
insufficient
or
poor
quality
combustion
air,
improper
vent
termination,
incorrect
size
or
damaged
manifold
orifice(s),
improper
gas,
or
a
restricted
heat
exchanger
(primary
or
secondary).
Action
must
be
taken
to
correct
the
problem.
1.
Turn
off
gas
and
electrical
supplies
to
furnace.
A
A
SS
ELECTRICAL
SHOCK,
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death,
or
property
damage.
Before
installing,
modifying,
or
servicing
system,
main
electrical
disconnect
switch
must
be
in
the
OFF
position
and
install
a
lockout
tag.
There
may
be
more
than
one
disconnect
switch.
Lock
out
and
tag
switch
with
a
suitable
warning
label.
Verify
proper
operation
after
servicing.
A
A
SS
ELECTRICAL
SHOCK
AND
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Turn
off the
gas
and
electrical
supplies
to
the
furnace
and
install
lockout
tag
before
performing
any
maintenance
or
service.
Follow
the
operating
instructions
on
the
label
attached
to
the
furnace.
.
Remove
control
door.
Ww
.
Disconnect
wires
or
connectors
to
flame
rollout
switch,
gas
valve,
igniter,
and
flame
sensor.
4.
Using
backup
wrench,
disconnect
gas
supply
pipe
from
fur-
nace
gas
control
valve.
5.
Remove
two
screws
attaching
top
filler
plate
and
rotate
up-
wards
to
gain
access
to
screws
attaching
burner
assembly
to
cell
panel.
6.
Remove
screws
attaching
burner
assembly
to
cell
panel.
See
Fig.
63.
NOTE:
Burner
cover,
manifold,
gas
valve,
and
burner
assembly
should
be
removed
as
one
assembly.
7,
Clean
heat
exchanger
openings
with
a
vacuum
and
a
soft
brush.
See
Fig.
60.
NOTE:
After
cleaning,
inspect
the
heat
exchangers
to
ensure
they
are
free
of
all
foreign
objects
that
may
restrict
flow
of
combustion
products.
8.
Reverse
items
6
through
1
for
reassembly.
9,
Refer
to
furnace
wiring
diagram
and
reconnect
wires
to
flame
rollout
switch,
gas
valve,
igniter,
and
flame
sensor.
10.
Turn
on
gas
and
electrical
supplies
to
furnace.
11.
Check
furnace
operation
through
2
complete
heat
operating
cycles.
Look
at
burners.
Burner
flames
should
be
clear
blue,
almost
transparent.
See
Fig.
61.
12.
Check
for
gas
leaks.
CA
AUN
Le
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Never
purge
a
gas
line
into
a
combustion
chamber.
Never
test
for
gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap
solution
made
specifically
for
the
detection
of
leaks
to
check
all
connections.
A
fire
or
explosion
may
result
causing
property
damage,
personal
injury
or
loss
of
life.
13.
Replace
main
furnace
door.
Secondary
Heat
Exchangers
The
condensing
side
(inside)
of
the
secondary
heat
exchanger
CANNOT
be
serviced
or
inspected
without
complete
removal
of
the
heat
exchanger
assembly.
Detailed
information
on
heat
exchanger
removal
can
be
obtained from
your
Distributor.
WINTERIZATION
4&
CAUTION
UNIT
AND
PROPERTY
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
unit
component
or
property
damage.
If
the
furnace
is
installed
in
an
unconditioned
space
where
the
ambient
temperatures
may
be
32°
F
(0°
C)
or
lower,
freeze
protection
measures
must
be
taken
to
prevent
minor
property
or
product
damage.
Since
the
furnace
uses
a
condensing
heat
exchanger,
some
water
will
accumulate
in
the
unit
as
a
result
of
the
heat
transfer
process.
Therefore,
once
it
has
been
operated,
it
cannot
be
turned
off
and
left
off
for
an
extended
period
of
time
when
temperatures
will
59SC2A

Other manuals for Carrier 59SC2A

Related product manuals