EasyManua.ls Logo

Carrier 59SC2A - Gas Piping

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GAS
PIPING
CA
UN
Le
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Never
purge
a
gas
line
into
a
combustion
chamber.
Never
test
for
gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap
solution
made
specifically
for
the
detection
of
leaks
to
check
all
connections.
A
fire
or
explosion
may
result
causing
property
damage,
personal
injury
or
loss
of
life.
CA
UA
Le:
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Use
proper
length
of
pipe
to
avoid
stress
on
gas
control
manifold
and
gas
valve.
CA
AUN
Le
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Gas
valve
inlet
and/or
inlet
pipe
must
remain
capped
until
gas
supply
line
is
permanently
installed
to
protect
the
valve
from
moisture
and
debris.
Also,
install
a
sediment
trap
in
the
gas
supply
piping
at
the
inlet
to
the
gas
valve.
Gas
piping
must
be
installed
in
accordance
with national
and
local
codes.
Refer
to
current
edition
of
NFGC
in
the
U.S.A.
Refer
to
current
edition
of
NSCNGPIC
in
Canada.
Installations
must
be
made
in
accordance
with
all
authorities
having
jurisdiction.
If
possible,
the
gas
supply
line
should
be
a
separate
line
running
directly
from
meter
to
furnace.
NOTE:
Use
a
back-up
wrench
on
the
inlet
of
the
gas
valve
when
connecting
the
gas
line
to
the
gas
valve.
In
the state
of
Massachusetts:
1.
Gas
supply
connections
MUST
be
performed
by
a
licensed
plumber
or
gas
fitter.
2.
When
flexible
connectors
are
used,
the
maximum
length
shall
not
exceed
36
in.
(915
mm).
3.
When
lever
handle
type
manual
equipment
shutoff
valves
are
used,
they
shall
be
T-handle
valves.
4,
The
use
of
copper
tubing
for
gas
piping
is
NOT
approved
by
the
state of
Massachusetts.
Refer
to
Table
10
for
recommended
gas
pipe
sizing.
Risers
must
be
used
to
connect
to
furnace
and
to
meter.
Support
all
gas
piping
with
appropriate
straps,
hangers,
etc.
Use
a
minimum
of
1
hanger
every
6
ft.
(2
M).
Joint
compound
(pipe
dope)
should
be
applied
sparingly
and
only
to
male
threads
of
joints.
Pipe
dope
must
be
resistant
to
the
action
of
propane
gas.
CA
UN
Le:
FIRE
OR
EXPLOSION
HAZARD
A
failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
If
local
codes
allow
the
use
of
a
flexible
gas
appliance
connector,
always
use
a
new
listed
connector.
Do
not
use
a
connector
which
has
previously
served
another
gas
appliance.
Black
iron
pipe
shail
be
installed
at
the
furnace
gas
control
valve
and
extend
a
minimum
of
2-in.
(51
mm)
outside
the
furnace.
4
CAUTION
FURNACE
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
furnace
damage.
Connect
gas
pipe
to
furnace
using
a
backup
wrench
to
avoid
damaging
gas
controls
and
burner
misalignment.
An
accessible
manual
equipment
shutoff
vaive
MUST
be
installed
external
to
furnace
casing
and
within
6
ft.
(2
M)
of
furnace.
Install
a
sediment
trap
in
riser
leading
to
furnace
as
shown
in
Fig.
31.
Connect
a
capped
nipple
into
lower
end
of
tee.
Capped
nipple
should
extend
below
level
of
furnace
gas
controls.
Place
a
ground
joint
union
between
furnace
gas
control
valve
and
exterior
manual
equipment
gas
shutoff
valve.
A
1/8-in.
(3
mm)
NPT
plugged
tapping,
accessible
for
test
gauge
connection,
MUST
be
installed
immediately
upstream
of
gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff
valve.
Piping
should
be
pressure
and
leak
tested
in
accordance
with
the
current
addition
of
the
NFGC
in
the
United
States,
local,
and
national
plumbing
and
gas
codes
before
the
furnace
has
been
connected.
Refer
to
current
edition
of
NSCNGPIC
in
Canada.
After
all
connections
have
been
made,
purge
lines
and
check
for
leakage
at
furnace
prior
to
operating
furnace.
NOTE:
The
furnace
gas
control
valve
inlet
pressure
tap
connection
is
suitable
to
use
as
test
gauge
connection
providing
test
pressure
DOES
NOT
exceed
maximum
0.5
psig
(14-in.
w.c.)
stated
on
gas
control
valve.
See
Fig.
53.
If
pressure
exceeds
0.5
psig
(14-in.
w.c.),
gas
supply
pipe
must
be
disconnected
from
furnace
and
capped
before
and
during
supply
pipe
pressure
test.
If
test
pressure
is
equal
to
or
less
than
0.5
psig
(14-in.
w.c.),
turn
off
electric
shutoff
switch
located
on
furnace
gas
control
valve
and
accessible
manual
equipment
shutoff
valve
before
and
during
supply
pipe
pressure
test.
After
all
connections
have
been
made,
purge
lines
and
check
for
leakage
at
furnace
prior
to
operating
furnace.
The
gas
supply
pressure
shall
be
within
the
maximum
and
minimum
inlet
supply
pressures
marked
on
the
rating
plate
with
the
furnace
burners
ON
and
OFF.
Some
installations
require
gas
entry
on
right
side
of
furnace
(as
viewed
in
upflow).
See
Fig.
30.
Gas
Pipe
Grommet
For
direct
vent
(2-pipe)
applications,
the
knockout
for
the
gas
pipe
must
be
sealed
to
prevent
air
leakage.
Remove
the
knockout,
install
the
grommet
in
the
knockout,
then
insert
the
gas
pipe.
The
grommet
is
included
in
the
loose
parts
bag.
See
Fig.
30.
59SC2A

Other manuals for Carrier 59SC2A

Related product manuals