EasyManua.ls Logo

Carrier 59SC2A - System Airflow and Condensate Management; Air for Combustion and Ventilation

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CA
UN
Le:
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death
and/or
property
damage.
Do
not
install
the
furnace
on
its
back
or
hang
furnace
with
control
compartment
facing
downward.
Safety
control
operation
will
be
adversely
affected.
Never
connect
return-air
ducts
to
the
back
of
the
furnace.
See
Fig.
4.
Location
Relative
to
Cooling
Equipment
The
cooling
coil
must
be
installed
parallel
with,
or
on
the
downstream
side
of
the
unit
to
avoid
condensation
in
the
heat
exchangers.
When
installed
parallel
with
the
furnace,
dampers
or
other
flow
control
must
prevent
chilled
air
from
entering
the
furnace.
If
the
dampers
are
manually
operated,
they
must
be
equipped
with
means
to
prevent
operation
of
either
unit
unless
the
damper
is
in
the
full-heat
or
full-cool
position.
AIR
FOR
COMBUSTION
AND
VENTILATION
Introduction
Direct
Vent
(2-pipe)
Applications
When
the
furnace
is
installed
as
a
direct
vent
(2-pipe)
furnace,
no
special
provisions
for
air
for
combustion
are
required.
However,
other
gas
appliances
installed
in
the
space
with
the
furnace
may
require
outside
air
for
combustion.
Follow
the
guidelines
below
to
insure
that
other
gas
appliances
have
sufficient
air
for
combustion.
Non-Direct
Vent
(1-pipe)
Applications
When
the
furnace
is
installed
as
a
non-direct
vent
(1-pipe)
furnace,
it
will
be
necessary
to
insure
there
is
adequate
air
for
combustion.
Other
gas
appliances
installed
with
the
furnace
may
also
require
air
for
combustion
and
ventilation
in
addition
to
the
amount
of
combustion
air
and
ventilation
air
required
for
the
furnace.
Follow
the
guidelines
below
to
insure
that
the
furnace
and
other
gas
appliances
have
sufficient
air
for
combustion.
Ventilated
Combustion
Air
Applications
When
the
furnace
is
installed
using
the
ventilated
combustion
air
option,
the
attic
or
crawlspace
must
freely
communicate
with
the
outdoor
to
provide
sufficient
air
for
combustion.
The
combustion
air
pipe
cannot
be
terminated
in
attics
or
crawlspaces
that
use
ventilation
fans
designed
to
operate
during
the
heating
season.
If
ventilation
fans
are
present
in
these
areas,
the
combustion
air
pipe
must
terminate
outdoors
as
a
Direct
Vent/
2-Pipe
system.
All
air
for
combustion
is
piped
directly
to
the
furnace
from
a
space
that
is
well
ventilated
with
outdoor
air
(such
as
an
attic,
crawl space
or
equipment
closet)
and
the
space
is
well
isolated
from
the
living
space
or
garage.
In
addition,
other
gas
appliances
installed
in
the
space
with
the
furnace
may
require
outside
air
for
combustion.
Follow
the
guidelines
below
to
insure
that
the
roof
or
crawlspace
wails
have
sufficient
free
area
to
provide
sufficient
air
for
combustion
and
ventilation
for
the
furnaces.
The
guidelines
below
can
be
used
to
insure
that
other
gas
appliances
have
sufficient
air
for
combustion.
Provisions
for
adequate
combustion,
ventilation,
and
dilution
air
must
be
provided
in
accordance
with:
¢
U.S.A.
Installations:
Section
9.3
of
the
NFPA
54/ANSI
2223.1-2009
,
Air
for
Combustion
and
Ventilation
and
applicable
provisions
of
the
local
building
codes.
¢
Canada:
Part
8
of
the
CAN/CSA-B149.1-2010,
Venting
Systems
and
Air
Supply
for
Appliances.
4
CAUTION
FURNACE
CORROSION
HAZARD
Failure
to
follow
this
caution
may
result
in
furnace
damage.
Air
for
combustion
must
not
be
contaminated
by
halogen
compounds,
which
include
fluoride,
chloride,
bromide,
and
iodide.
These
elements
can
corrode
heat
exchangers
and
shorten
furnace
life.
Air
contaminants
are
found
in
aerosol
sprays,
detergents,
bleaches,
cleaning
solvents,
salts,
air
fresheners,
and
other
household
products.
CA
UA
Le:
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
The
operation
of
exhaust
fans,
kitchen
ventilation
fans,
clothes
dryers,
attic
exhaust
fans
or
fireplaces
could
create
a
NEGATIVE
PRESSURE
CONDITION
at
the
furnace.
Make-up
air
MUST
be
provided
for
the
ventilation
devices,
in
addition
to
that
required
by
the
furnace.
Refer
to
the
Carbon
Monoxide
Poisoning
Hazard
warning
in
the
venting
section
of
these
instructions
to
determine
if
an
adequate
amount
of
make-up
air
is
available.
The
requirements
for
combustion
and
ventilation
air
depend
upon
whether
or
not
the
furnace
is
located
in
a
space
having
a
volume
of
at
least
50
cubic
feet
per
1,000
Btuh
input
rating
for
all
gas
appliances
installed
in
the
space.
¢
Spaces
having
less
than
50
cubic
feet
per
1,000
Btuh
(4.8
cubic
meters
per
kW)
require
the
Outdoor
Combustion
Air
Method.
¢
Spaces
having
at
least
50
cubic
feet
per
1,000
Btuh
(4.8
cubic
meters
per
kW)
may
use
the
Indoor
Combustion
Air,
Standard
or
Known
Air
Infiltration
Method.
Outdoor
Combustion
Air
Method
1.
Provide
the
space
with
sufficient
air
for
proper
combustion,
ventilation,
and
dilution
of
flue
gases
using
permanent
hori-
zontal
or
vertical
duct(s)
or
opening(s)
directly
communicat-
ing
with
the
outdoors
or
spaces
that
freely
communicate
with
the
outdoors.
.
Fig.
6
illustrates
how
to
provide
TWO
OUTDOOR
OPENINGS,
one
inlet
and
one
outlet
combustion
and
vent-
ilation
air
opening,
to
the
outdoors.
bo
a.
One
opening
MUST
commence
within
12
in.
(300
mm)
of
the
ceiling
and
the
second
opening
MUST
commence
within
12
in.
(300
mm)
of
the
floor.
b.
Size
openings
and
ducts
per
Fig.
6
and
Table
3.
c.
TWO
HORIZONTAL
DUCTS
require
1
sq.
in.
(645
sq.
mm)
of
free
area
per
2,000
Btuh
(1,100
mm2/kW)
of
com-
bined
input
for
all
gas
appliances
in
the
space
per
Fig.
6
and
Table
3.
d.
TWO
OPENINGS
OR
VERTICAL
DUCTS
require
1
sq.
in.
(645
sq.
mm)
of
free
area
per
4,000
Btuh
(550
mm_2/kW)
for
combined
input
of
all
gas
appliances
in
the
space
per
Fig.
6
and
Table
3.
3.
ONE
OUTDOOR
OPENING
requires:
a.
1
sq.
in.
(645
sq.
mm)
of
free
area
per
3,000
Btuh
(734
mm_2/kW)
for
combined
input
of
all
gas
appliances
in
the
space
per
Fig.
6
and
Table
3.
b.
Not
less
than
the
sum
of
the
areas
of
all
vent
connectors
in
the
space.
59SC2A

Other manuals for Carrier 59SC2A

Related product manuals