EasyManua.ls Logo

Carrier 59SC2A - Sequence of Operation

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEQUENCE
OF
OPERATION
NOTE:
Furnace
control
must
be
grounded
for
proper
operation
or
control
will
lock
out.
Control
is
grounded
through
green/yellow
wire
routed
to
gas
valve
and
manifold
bracket
screw.
Using
the
schematic
diagram
in
Fig.
65,
follow
the
sequence
of
operation
through
the
different
modes.
Read
and
follow
the
wiring
diagram
very
carefully.
NOTE:
Ifa
power
interruption
occurs
during
a
call
for
heat
(W),
the
control
will
start
a
90-sec
blower-only
ON
period
two
sec
after
power
is
restored,
if
the
thermostat
is
still
calling
for
gas
heating.
The
Amber
LED
light
will
flash
code
12
during
the
90-sec
period,
after
which
the
LED
will
be
ON
continuous,
as
long
as
no
faults
are
detected.
After
the
90-sec
period,
the
furnace
will
respond
to
the
thermostat
normally.
The
blower
door
must
be
installed
for
power
to
be
conducted
through
the
blower
door
interlock
switch
ILK
to
the
furnace
control
CPU,
transtormer
TRAN,
inducer
motor
IDM,
blower
motor
BLWM,
hot-surface
igniter
HSI,
and
gas
vaive
GV.
1.
Heating
See
Fig.
36
for
thermostat
connections.)
The
wail
thermostat
“calls
for
heat,”
closing
the
R-to-W
circuit.
The
furnace
control
performs
a
self-check,
verifies
the
pressure
switch
contacts
LPS
and
HPS
are
open,
and
starts
the
inducer
motor
IDM.
a.
Inducer
Prepurge
Period-
As
the
inducer
motor
IDM
comes
up
to
speed,
the
low
pressure
switch
contacts
LPS
close
to
begin
a
15-sec
prepurge
period.
The
high
pressure
switch
contacts
HPS
are
ignored
until
one
minute
after
the
gas
valve
closes.
b.
Igniter
Warm-Up-
At
the
end
of
the
prepurge
period,
the
Hot-Surface
igniter
HSI
is
energized
for
a
17-sec
igniter
warm-up
period.
c.
Trial-for-Ignition
Sequence-
When
the
igniter
warm-
up
period
is
completed,
the
main
gas
valve
relay
contacts
GVR
close
to
energize
the
gas
valve
GV,
the
gas
valve
opens,
and
24
vac
power
is
supplied
for
a
field-installed
humidifier
at
the
HUM
terminal.
The
gas
valve
GV
permits
gas
flow
to
the
burners
where
it
is
ignited
by
the
HSI.
Five
sec
after
the
GVR
closes,
a
2-sec
flame
proving
period
be-
gins.
The
HSI
igniter
will
remain
energized
until
the
flame
is
sensed
or
until
the
2-sec
flame
proving
period
begins.
d.
Flame-Proving-
When
the
bumer
flame
is
proved
at
the
flame-proving
sensor
electrode
FSE,
the
furnace
control
CPU
begins
the
blower-ON
delay
period
and
continues
to
hold
the
gas
valve
GV
open.
If
the
burner
flame
is
not
proved
within
two
sec,
the
control
CPU
will
close
the
gas
valve
GV,
and
the
control
CPU
will
repeat
the
ignition
se-
quence
for
up
to
three
more
Trials-For-Ignition
before
go-
ing
to
Ignition-Lockout.
Lockout
will
be
reset
automatic-
ally
after
three
hours
or
by
momentarily
interrupting
115
vac
power
to
the
furnace,
or
by
interrupting
24
vac
power
at
SEC1
or
SEC2
to
the
furnace
control
CPU
(not
at
W,
G,
R,
etc.).
If
flame
is
proved
when
flame
should
not
be
present,
the
furnace
control
CPU
will
lock
out
of
Gas-Heating
mode
and
operate
the
inducer
motor
IDM
until
flame
is
no
longer
proved.
e.
Blower-On
Delay-
If
the
burner
flame
is
proven,
the
blower
motor
is
energized
on
HEAT
speed
25
sec
after
the
gas
valve
GV
is
energized.
Simultaneously,
the
electronic
air
cleaner
terminal
EAC-1
is
energized
and
remains
energized
as
long
as
the
blower
motor
BLWM
is
energized.
f.
Blower-Off
Delay-
When
the
thermostat
is
satisfied,
the
R-to-W
circuit
is
opened,
de-energizing
the
gas
valve
GV,
stopping
gas
flow
to
the
burners,
and
de-energizing
the
hu-
midifier
terminal
HUM.
The
inducer
motor
IDM
will
re-
main
energized
for
a
15-sec
post-purge
period.
The
blower
motor
BLWM
and
air
cleaner
terminal
EAC-1
will
remain
energized
for
90,
120, 150,
or
180
sec
(depending
on
the
blower-OFF
delay
selection).
The
furnace
control
CPU
is
factory-set
for
a
120-sec
blower-OFF
delay.
2.
Cooling
Mode
The
thermostat
“calls
for
cooling.”
See
Fig.
36
for
thermostat
connections)
The
thermostat
closes
the
R-to-G-and-Y
circuits.
The
R-to-
Y
circuit
starts
the
outdoor
unit,
and
the
R-to-G-and-Y
circuits
start
the
furnace
blower
motor
BLWM
on
COOL
speed.
The
electronic
air
cleaner
terminal
EAC-1
is
energized
with
115
vac
when
the
blower
motor
BLWM
is
operating.
When
the
thermostat
is
satisfied,
the
R-to-G-and-Y
circuits
are
opened.
The
outdoor
unit will
stop,
and
the
furnace
blower
motor
BLWM
will
continue
operating
on
the
COOL
speed
for
an
additional
90
sec.
3.
Continuous
Blower
Mode
When
the
R-to-G
circuit
is
closed
by
the
thermostat,
the
blower
motor
BLWM
will
operate
on
HEAT
speed.
Ter-
minal
EAC-1
is
energized
as
long
as
the
blower
motor
BLWM
is
energized.
During
a
call
for
heat,
the
blower
BLWM
will
stop
during
igniter
warm-up
(17
sec),
ignition
(7
sec),
and
blower-ON
delay
(25
sec),
allowing
the
furnace
heat
exchangers
to
heat
up
more
quickly,
then
restarts
at
the
end
of
the
blower-ON
delay
period
at
HEAT
speed.
When
the
thermostat
“calls
for
cooling”,
the
blower
motor
BLWM
will
operate
at
COOL
speed.
When
the
thermostat
is
satisfied,
the
blower
motor
BLWM
will
operate
an
addi-
tional
90
sec
on
COOL
speed
before
reverting
back
to
con-
tinuous-blower
(HEAT
speed).
When
the
R-to-G
circuit
is
opened,
the
blower
motor
BLWM
will
continue
operating
for
an
additional
5
sec,
if
no
other
function
requires
blower
motor
BLWM
operation.
4.
Heat
Pump
When
installed
with
a
heat
pump,
the
furnace
control
auto-
matically
changes
the
timing
sequence
to
avoid
long
blower
off
times
during
demand
defrost
cycles.
When
the
R-to-
Wand-
Y
or
R-to-W-and-Y-and-G
circuits
are
energized
the
furnace
control
CPU
will
continue
to
turn
on
the
blower
motor
BLWM
at
HEAT
speed,
and
begin
a
heating
cycle.
The
blower
motor
BLWM
will
remain
on
until
the
end
of
the
prepurge
period,
then
shut
off
for
24
sec
then
come
back
on
at
HEAT
speed.
When
the
W
input
signal
disappears,
the
furnace
control
begins
a
normal
inducer
post-purge
period
and
the
blower
switches
to
COOL
speed
after
a
3
sec
delay.
If
the
R-to-W-and-Y-and-G
signals
disappear
at
the
same
time,
the
blower
motor
BLWM
will
remain
on
for
the
selec-
ted
blower-
OFF
delay
period.
If
the
R-to-W-and-Y
sig-
nals
disappear,
leaving
the
G
signal,
the
blower
motor
BLWM
will
continue
running
the
blower
motor
at
HEAT
speed
after
the
selected
blower-OFF
delay
period
is
com-
pleted.
Component
Self-Test
Refer
to
page
71
for
instructions.
79
59SC2A

Other manuals for Carrier 59SC2A

Related product manuals