Table 8 — Control Manual Graphics
HUMIDITY OPTIONS #1
Determine what humidity sensors the 62X supply control will
look for. Common configurations include:
OARH, SARH - for units without ECW. Unit will have
outdoor air and supply air relative humidity sensors
OARH, ECRH, SARH - for units with ECW. Unit will
have outdoor air, entering coil (after ECW), and supply air
relative humidity sensors
All others - not used with 62X.
AIR PRESSURE OPTIONS
Determine what DPT sensors the 62X control will look for. Com-
mon configurations include:
SF DPT - supply fan differential pressure transmitter
(duct)
ZN DPT - zone (building) differential pressure transducer.
Can be used with supply fan or exhaust fan (not both)
EF DPT - exhaust fan differential pressure transmitter
(duct), not used with 62X.
Archive Program
The program archive screen (Home
Setup

isc Settings
Archive) displays the control program archive status, archive
date, current time and date, and update archive option. See
Fig. 52. The controller can store two program archives in memo-
ry. One slot is filled upon program installation, which usually oc-
curs in the factory. The second can be filled by a field-initiated ar-
chive. Use the Archive screen to check current archive status, cur-
rent archive date, current archive number, and to archive the
program.
OPTION
STATUS
OPTION
STATUS
VALUE DISPLAY VALUE DISPLAY
SF Option
1 None
Cooling Enabled By
1 OAE
2 Included 2 OAT
3 SFVFD AMS 3 OAT and OADP
4 SFVFD CAV 4 OAT or OAE
5 SFVFD DPT (ZN, Bldg) 5 OAT/SAT vs SAT
6 SFVFD DPT (Duct) 6 RAT
7 SFVFD ZAT 7 ZAT
EF Option
1 None 8 None
2 Included
Heating Enabled By
1 OAT
3 EFVFD AMS 2 OAT/SAT vs SAT
4 EFVFD CAV 3 RAT
5 EFVFD DPT (ZN, Bldg) 4 ZAT
6 EFVFD DPT (Duct) 5 None
7 EFVFD ZAT
Temp Option #1
1 None
HGRH Option
1 Lead On-Off 2 ECAT
2 Lead On-Off, SC 3 OAT
3 Lead Mod. 4 SAT ECAT, OAT
4 Lead Mod., SC 5 ECAT, SAT
5 Both On-Off 6 OAT, SAT
6 Both Mod. 7 ECAT, OAT, SAT
7 By Heating Only
Temp Option #2
1 None
Dehum Option
1 None 2 RAT
2 ECPD VS SADP SP 3 WExAT
3 ECAE 4 RAT, WExAT
4 MADP
Humidity Option #1
1 None
5 MAE 2 ECRH
6 OADP vs SADP SP 3 OARH
7 OAE 4 SARH
8 RARH 5 ECRH, OARH
9 SARH 6 ECRH, SARH
10 ZADP 7 OARH, SARH
11 Z-RH 8 ECRH, OARH, SARH
Heating Option
1 None
Humidity Option #2
1 None
2 Elec., 1 Stg 2 RARH
3 Elec., 2 Stg
Air Pressure Options
1 None
4 Elec., 3 Stg 2 EF-DPT
5 Elec., 4 Stg 3 SF-DPT
6 Elec., SCR 4 ZN-DPT
7 Gas, 2 STG 5 EF-DPT, SF-DPT
8 Gas, 4 Stg 6 EF-DPT, ZN-DPT
9 Gas, 8 Stg 7 SF-DPT, ZN-DPT
10 Gas, Mod 8 EF, SF, ZN-DPT
11 Hot Water
12 Steam