EasyManua.ls Logo

Carrier 62X Series - Supply Air Temperature and Relative Humidity Sensor (SAT;RH); SAT;RH SENSOR INSTALLATION; SENSOR MOUNTING; SENSOR WIRING AND CONFIGURATION

Carrier 62X Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
Supply Air Temperature and Relative Humidity
Sensor (SAT/RH)
All 62X units require a SAT/RH sensor for operation. See
Table 14 for sensor details. On 62X units with a factory installed
heater, the SAT/RH sensor ships in the control enclosure for field
mounting, wiring, and installation on the supply duct work. See
below for installation instructions and see Fig. 70 for sensor di-
mensions. The SAT/RH sensor should be installed at least 10 feet
away from the unit, to ensure a proper reading.
On units without factory installed heat, the SAT/RH sensor is fac-
tory installed. Note - if a field provided duct heat source is used,
the factory SAT/RH sensor must be located to at least 10 feet
downstream of the heat source.
The SAT/RH sensor requires four conductors. Two conductors are
connected to UI-3 for the SAT sensor input. See Table 15 for
thermistor resistance readings. The other two conductors are used
to for the SARH sensor power (24V can be taken from TB-A) and
the output, which is connected to the UI-4 input on the OEMCtrl
OptiCORE LS-1628u controller. See Fig. 70 for SAT/RH sensor
and controller wiring details.
Fig. 70 — SAT/RH Sensor Dimensions
SAT/RH SENSOR INSTALLATION
SENSOR MOUNTING
The transmitter installs directly into any air duct with a
minimum width/diameter of 10 inches.
Select a suitable installation area in the middle of the duct
wall.
- To achieve the best reading, do not place in an area
where air stratification may be present.
- Mount the sensor at least 5 foot in either direction from
elbows, dampers, filters or other duct restrictions.
- Avoid areas where the transmitter is exposed to
vibrations or rapid temperature changes.
Once a suitable spot is selected, drill a 0.6 in. to 0.75 in.
hole for the probe.
Slide the probe in the drilled hole until the enclosure is
flush against the duct.
- The airflow direction is not important.
- A foam gasket on the back of the enclosure provides a
seal against air leaks.
Secure the enclosure to the duct with (2) #10 x 1 in. self-
tapping screws (Not provided).
Tighten screws until the enclosure is tight against the duct
and that there is no movement of the enclosure
SENSOR WIRING AND CONFIGURATION
Using a Phillips screwdriver, remove the (2) screws hold-
ing the cover on the sensor
Remove cover and set aside with screws for re-installing
after wiring and set up.
Two 0.8125 in. holes are provided for connection of either
0.5 in. EMT or a cable gland style connector
Insert the EMT or cable gland connector through the hole
and securely fasten using a locknut.
- If only one connection hole is required, use the included
hole cap to cap the unused opening.
Special care must be taken not to damage any internal
components during installation.
Deactivate the 24 VAC/DC power supply until all connec-
tions are made to the device to prevent electrical shock or
equipment
Use 14-22 AWG shielded wiring for all wiring connections
- Do not locate the device wires in the same conduit with
wiring used to supply inductive loads such as motors.
- The humidity and temperature connections can be made
using a single, multi conductor, shielded cable if
desired.
- Make all connections in accordance with national and
local codes.
Pull at least six inches of wire into the enclosure, then
complete the wiring connection per Fig. 71.
Connect the DC positive or the AC voltage hot side to the
PWR terminal.
- For voltage output or AC power, the supply Common is
connected to the COM terminal.
- The device is reverse voltage protected and will not
operate if connected backwards.
The analog output is available on the OUT terminal. Check
the controller Analog Input to determine the proper con-
nection before applying power as shown in Fig. 6.
The resistance temperature output is available on the two
terminals labeled TEMPERATURE SENSOR as shown in
Fig. 71.
A jumper may be used between the TEMPERATURE
SENSOR and COM to reduce the number of needed con-
ductors.
Table 14 — Sensor
Sensor Name
Greystone/ACI RH200A Duct
Temperature and Relative Humidity
Transmitter
Factory Part Number 0843P-0586
Sensor Type
Temperature: Thermistor, 10K (at
77°F)Humidity: Thermoset Polymer
Capacitive
Sensor Range
Temperature: –4 to 221°F
Humidity: 0 to 100%
Operating Range -40 to 185°F
Output Signal
Temperature: Resistive
Humidity: 0 to 10V
Power Supply 18 to 30 VDC, 15 to 26 VAC
Probe Dimensions 9 in. long, 5 in. diameter
Wire Size 14-22 AWG
3.320
[84.3]
2X Ø 0.850"
2.110
[53.6]
4.56
[115.8]
9
[228.6]
0.50
[12.70]
60 micron HDPE filter
304 Series S/S Probe

Table of Contents

Related product manuals