Carrier 62X Series - Fig. 100 - Wiring Diagram for Units with Inverter Driven Compressor (20+ tons) (cont)

Carrier 62X Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
78
Fig. 100 — Wiring Diagram for Units with Inverter Driven Compressor (20+ tons) (cont)
261
WIRING DIAGRAM #62X W/O ERV,VFD COMPWD | 62X420 | Dedicated Outside Air System | Air Source Cooling | 460-3-60 | SHEET 5 OF 7 | 06/08/21 DWN
SRF
CHK
LWF
.
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
Install Condensate Overflow
Switch “COS” At Lowest
Po int of Drain Pan
FACTORY WIRING
FIELD WIRING
TERMINAL BOARD
SYMBOL LEGEND
WIRE ALL SHIELD WIRES TO CLOSEST TB-A or TB-D
“GND” TERMINAL AT THE CONTROL PANEL
4
-A (Adj.)
NO COM
OADA
-A (Adj.)
NO COM
OADA
LP1LP1
9
5
HPR1
9
5
HPR1
LP2LP2
9
5
HPR2
9
5
HPR2
EF-CSEF-CS
CC1-CSCC1-CS
CC2-CSCC2-CS
SF-CSSF-CS
COSCOS
1
3
CFI
1
3
CFI
18
10 9
7
SD
18
10 9
7
SD
ECM Motors
With the ALC off (power must be supplied to
the motor), turn the pot enometer clockwise
unl the “RED LED” is lit. Turn the
potenometer counter-clockwise unl the
“RED LED” turns off and the “BLUE LED” is lit.
Please note that with very small loads the
“BLUE LED” will be very dim.
ECM Motors
With the ALC off (power must be supplied to
the motor), turn the pot enometer clockwise
unl the “RED LED” is lit. Turn the
potenometer counter-clockwise unl the
“RED LED” turns off and the “BLUE LED” is lit.
Please note that with very small loads the
“BLUE LED” will be very dim.
Adjustable Current Switch AdjusmentAdjustable Current Switch Adjusment
AC Motors and Compressors
With the motor or compressor on and at its
lowest speed turn the potenometer
clockwise unl the “RED LED” is lit.
AC Motors and Compressors
With the motor or compressor on and at its
lowest speed turn the potenometer
clockwise unl the “RED LED” is lit.
If th e “RED LED” fails to turn on wh ile th e
motor is in operaon and the current switch is
at its lowest adjustment addional wraps of
wire may be needed.
If th e “RED LED” fails to turn on wh ile th e
motor is in operaon and the current switch is
at its lowest adjustment addional wraps of
wire may be needed.
+
Aux
AuxUniversal Inputs
Universal Inputs Universal Inputs
TB1
R C
R BL
BK
BK
PR
PR
PK
PK
W
W
BR
O
GY
BK
Y
Y
W
W
BK
GY
O
BR
PK
PK
PR
PR
4
2
BK
Install OA-T/RH under the
OA hood, sensing the
am bi ent tem p /humidit y.
2
G
DxLAT2: INSTALL AFTER DX COIL
#2 UPSTREAM OF REHEAT COIL
R
BK
DxLAT1: INSTALL AFTER DX COIL
#1 UPSTREAM OF REHEAT COIL
Field install
and wire
1
4
Note: THE SUPPLY/DISCHARGE AIR TEMPERATURE/RELI TIVE HUMI DITY
(SA-T/RH) IS FACTORY SUPPLIED FOR FIELD INSTALLATION IN SUPPLY AIR
DUCT. SENSOR MUST BE INSTALLED DOWNSTREAM OF HEATER WHERE
IT CANNOT “SEE” ANY HEATING ELEMENTS AND WHERE SUFFICIENT
MIX ING OF D IS CH ARGE AIR OCCU RS. USE 18 A WG SHIE LDED WI RE. DO
NOT RUN SENSOR WIR ING IN THE SAME CO NDUIT AS LINE V OL TAGE
WIRING O R WITH WIRING THAT SWITCHES HIGHL Y INDUCTI VE LO ADS
SUCH AS CO NTACTOR AN D RELAY CO ILS.
1
W
4
R
BK
4
4
4
BU ILDIN G STATIC
St a c P re ssure Sens or
Field install and wire
Stac P re ssure Sensor
Field install and wire
0-10vdc out
COM
EXC
ALL FIELD INSTALLED SENSORS SHOULD BE WIRED TO THE
CONTROLLER FOR FACTORY TESTING WITH TEMPORARY
WIRING AND LEFT IN THE UNIT AFTER TEST. TEMPORARY
WIRING SHOULD BE REMOVED FOR PERMANENT
INSTALLATION DURING UNIT INSTALLATION. LABEL
SENSORS PER THE WIRING DIAGRAM.
SF-DPTSF-DPT
DXLAT1DXLAT1
DXLAT2DXLAT2
temp
sen sor
V
ou t
co m
V in
pwr
OA-T/RH
temp
sen sor
V
ou t
co m
V in
pwr
OA-T/RH
temp
sen sor
V
ou t
co m
V in
pwr
SA-T/RH
temp
sen sor
V
ou t
co m
V in
pwr
SA-T/RH
0-10vdc o ut
COM
EXC
ZN-DPT
0-10vdc o ut
COM
EXC
ZN-DPT
SENSORS Line # DESCRIPTION
CFI 383 Clogged Filter Indicator
COS 385 Condensate Overflow Switch
DXLAT1, DXLAT2 345,347 Dx Leaving Air Temperature #1, #2
OA-T/RH 327 Outside Air - Tempature & Humidity
SA-T/RH 331 Supply Air - Temperature & Humidity
SD 387 Factor Installed Smoke Detector
SF-DPT 349 Supply Fan - Differenal Pressure Transducer
ZN-DPT 351
ZONE (Space) - Differenal Pressure Transducer
ZS SENSOR 268 ZS Room Sensor
R
Temperature/Humidity Sensor Details
GreyStone
ACI
PWR
OUT
COM
TEMP
VOUT
COM
4-20mA
(Unused)
VIN
G
WH
Loose Wires for
Tempature s ensor
BK
G
W
R
R
W
BK
G
Factory Wired Colors
R
temp
sen sor
V
ou t
co m
V in
pwr
temp
sen sor
V
ou t
co m
V in
pwr
Set swit ch to V OLTS
Set J umpe r t o 10V