PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Refer  to  the  instructions  supplied  with  the  external  filter  rack  for
assembly and installation options. 
AIR DUCTS 
GENERAL REQUIREMENTS 
The  duct  system  should  be  designed  and  sized  according  to  accepted
national  standards  such  as  those  published  by:  Air  Conditioning
Contractors  Association  (ACCA),  Sheet  Metal  and  Air  Conditioning
Contractors  National Association  (SMACNA)  or American  Society  of
Heating,  Refrigerating  and Air  Conditioning  Engineers  (ASHRAE)  or
consult  The  Air  Systems  Design  Guidelines  reference  tables  available
from your local distributor. The duct system should be sized to handle
the required system design CFM at the design external static pressure.
The  furnace  airflow  rates  are  provided  in  Table 4-Air  Delivery-CFM
(With Filter). When a furnace is installed so that the supply ducts carry
air  circulated  by  the  furnace  to  areas  outside  the  space  containing  the
furnace,  the  return  air  shall  also  be  handled  by  duct(s)  sealed  to  the
furnace casing and terminating outside the space containing the furnace. 
Secure ductwork with proper fasteners for type of ductwork used. Seal
supply- and return-duct connections to furnace with code approved tape
or duct sealer.
NOTE:  Flexible  connections  should  be  used  between  ductwork  and
furnace to prevent transmission of vibration. 
Ductwork  passing  through  unconditioned  space  should  be  insulated  to
enhance  system  performance.  When  air  conditioning  is  used,  a  vapor
barrier is recommended. 
Maintain  a  1-in.  (25  mm)  clearance  from  combustible  materials  to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from
the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment 
NOTE: Metal duct systems that do not have a 90 degree elbow and 10
ft. (3  M)  of main duct to the first branch take-off may require internal
acoustical  lining. As  an  alternative,  fibrous  ductwork  may  be  used  if
constructed  and  installed  in  accordance  with  the  latest  edition  of
SMACNA construction standard on fibrous glass ducts. Both acoustical
lining and fibrous ductwork shall comply with NFPA  90B as tested by
UL Standard 181 for Class 1 Rigid air ducts. 
SUPPLY AIR CONNECTIONS 
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided  with  a  removable  access  panel.  This  opening  shall  be
accessible when the furnace is installed and shall be of such a size that
the  heat  exchanger  can  be  viewed  for  possible  openings  using  light
assistance or  a  probe  can  be  inserted  for  sampling the  air stream. The
cover attachment shall prevent leaks. 
Upflow and Horizontal Furnaces 
Connect  supply-air  duct  to  flanges  on  furnace  supply-air  outlet.  Bend
flange upward to 90° with wide duct pliers. (See Fig. 17). The supply-air
duct  must  be  connected  to  ONLY  the  furnace  supply-outlet-air  duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace  casing  side  to  attach  supply  air  duct,  humidifier,  or  other
accessories. All  accessories  MUST  be  connected  to  duct  external  to
furnace main casing. 
NOTE:  For  horizontal  applications,  the  top  most  flange  may  be  bent
past 90° to allow the evaporator coil to hang on the flange temporarily
while the remaining attachment and sealing of the coil are performed. 
Downflow Furnaces
Connect  supply-air  duct  to  supply-air  outlet  on  furnace.  Bend  flange
inward past 90° with wide duct pliers (See Fig. 17). The supply-air duct
must be connected to ONLY the furnace supply outlet or air conditioning
coil  casing  (when  used).  When  installed  on  combustible  material,
supply-air  duct  must  be  connected  to  ONLY  the  factory-approved
accessory  subbase,  or  a  factory-approved  air  conditioning  coil  casing.
DO  NOT  cut  main  furnace  casing  to  attach  supply  side  air  duct,
humidifier, or other accessories. All accessories MUST be connected to
duct external to furnace casing. 
A190346
Fig. 17 – Duct Flanges
RETURN AIR CONNECTIONS 
Downflow Furnaces
The return-air duct must be connected to return-air opening bottom inlet.
(See Fig. 1). DO NOT cut into casing sides (left or right). Side opening
is  permitted  for  only  upflow  and  certain  horizontal  furnaces.  Bypass
humidifier connections should be made at ductwork or coil casing sides
exterior to furnace. (See Fig. 18). 
Upflow and Horizontal Furnaces 
The return-air duct must be connected to bottom, sides (left or right), or a
combination of bottom and side(s) of main furnace casing. (See Fig. 1).
Bypass  humidifier  may  be  attached  into  unused  return  air  side  of  the
furnace casing. (See Fig. 19 and Fig. 20). Not all upflow and horizontal
furnace models are approved for side return air connections. (See Fig. 19
and Fig. 20). 
WARNING
!
FIRE HAZARD
A  failure  to  follow  this  warning  could  cause  personal  injury,  death
and/or property damage. 
Never  connect  return-air  ducts  to  the  back  of  the  furnace.  Follow
instructions below.
UPFLOW/
HORIZONTAL
DOWNFLOW