PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
 
A03182
Fig. 33 – Dual-Fuel Thermostat with Two-Stage Furnace and 
Two-Speed Heat Pump
 
A03183
Fig. 34 – Two-Stage Thermostat with Two-Stage Furnace and 
Two-Speed Air Conditioner
 
A03184
Fig. 35 – Single-Stage Thermostat with Two-Stage Furnace and 
Two-Speed Air Conditioner
NOTES FOR FIGURES 28 - FIGURES 35:
1. Heat  pump  MUST  have  a  high  pressure  switch  for  dual  fuel
applications.
2. Refer to outdoor equipment Installation Instructions for additional
information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the “ZONE”
position on the  two-speed heat  pump control. Heat pumps having
date  codes  1601E  and  later  do  not  have  or  require  a  “ZONE”
selection.
4. Outdoor Air Temperature Sensor must be attached in  all dual  fuel
applications.
5. Dip switch No. 1 on Thermidistat should be set in OFF position for
air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for
heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for
single-speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for
two-speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned
ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when
using a Thermidistat. 
11. Optional  connection:  If  wire  is  connected,  dip  switch  SW1-2  on
furnace  control  should  be  set  in  ON  position  to  allow
Thermidistat/Thermostat to control furnace staging.
12. Optional  connection:  If  wire  is  connected,  ACRDJ  jumper  on
furnace  control  should  be  removed  to  allow
Thermidistat/Thermostat to control outdoor unit staging.
13. Furnace  must  control  its  own  high-stage  heating  operation  via
furnace control algorithm.
14. The  RVS  Sensing  terminal  “L”  should  not  be  connected. This  is
internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE
POINT” option on the two-speed heat pump control board. This is
controlled internally by the Thermidistat/Dual Fuel Thermostat.
16. Dip  switch  D  on  Dual  Fuel  Thermostat  should  be  set  in  OFF
position  for  single-speed  compressor  operation.  This  is  factory
default.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position
for two-speed compressor operation.
7
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17
on the page following these figures
See notes 2, 11, and 12 on the
page following these figures
See notes 1 and 2 on the page
following these figures