PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
 
A02068
Fig. 50 – Horizontal Right Application-Vent Elbow Left
Venting Notes for Fig. 38 - Fig. 50
1. For common vent, vent connector sizing and vent material: United
States--use the NFGC.
2. Immediately  increase  to  5-in.  (102  mm)  or  6-in.  (152  mm)  vent
connector  outside  furnace  casing  when  5-in.  (127  mm)  vent
connector is required, refer to Note 1 above.
3. Side  outlet  vent  for  upflow  and  downflow  installations  must  use
Type  B  vent  immediately  after  exiting  the  furnace,  except  when
factory-approved  Downflow  Vent  Guard  Kit  is  used  in  the
downflow position. See Product Data Sheet for accessory listing.
4. Type-B vent where required, refer to Note 1 above.
5. A 4-in.(102 mm) single-wall (26 ga. min.) vent must be used inside
furnace  casing  and  when  the  factory-approved  Downflow  Vent
Guard Kit is used external to the furnace.  See Product Data Sheet
for accessory listing.
6. Accessory  Downflow  Vent  Guard  Kit  required  in  downflow
installations with lower vent configuration. See Product Data Sheet
for accessory listing.
7. Chimney  Adapter  Kit  may  be  required  for  exterior  masonry
chimney applications. Refer to Chimney Adapter Kit for sizing and
complete application details. See Product Data Sheet for accessory
listing.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant
sheet metal screws, spaced approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion
resistant screws  spaced  approximately  120_ apart. Secure Type-B
vent  connectors  per  vent  connector  manufacturer’s
recommendations.
START-UP, ADJUSTMENT, AND SAFETY 
CHECK 
GENERAL 
1. Maintain 115-v wiring and ground. Improper polarity will result in
rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24-v terminal block on the
furnace control.  Failure  to make  proper  connections will result  in
improper operation. (See Fig. 24 - Fig. 36).
3. Gas  supply  pressure  to  the  furnace  must  be  greater  than  4.5-In.
W.C. (0.16 psig ) but not exceed 14-In. W.C. (0.5 psig).
4. Check all manual-reset switches for continuity.
5. Replace  blower  compartment  door.  Door  must  be  in  place  to
operate furnace.
6. Setup switch descriptions. The  variable  speed  furnace control has
DIP switches to select thermostat staging, blower off delay timings,
air flow selection and other operational or service related functions.
(See Fig. 36, Fig. 54, and Fig. 59).
START-UP PROCEDURES 
1. Purge gas lines after all connections have been made. 
2. Check gas lines for leaks. 
3. To Begin Component Self-Test: 
a. Remove Blower Access Door. 
b. Disconnect the thermostat R lead from furnace control board.
c. Manually close blower door switch. 
d. Turn Setup DIP switch SW1-6 ON. (See Fig. 36, Fig. 54, and 
Fig. 59). 
NOTE:  The  furnace  control  allows  all  components,  except  the  gas
valve, to be run for short period of time. This feature helps diagnose a
system problem in case of a component failure. Component test feature
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury. 
Sheet  metal  parts  may have  sharp edges  or  burrs.  Use care  and wear
appropriate  protective  clothing,  safety  glasses  and  gloves  when
handling parts, and servicing furnaces. 
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death or
property damage. 
This  furnace  is equipped  with  manual  reset  limit  switches  in  the  gas
control area. The switches open and shut off power to the gas valve, if a
flame rollout  or  overheating condition occurs  in the  gas control  area.
DO  NOT  bypass  the  switches.  Correct  problem  before  resetting  the
switches. 
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death. 
Blower  access  door  switch  opens  115-v  power  to  control.  No
component operation can occur unless switch is closed. Caution must
be taken when manually closing this switch for service purposes.