PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
GAS PIPING 
Gas  piping  must  be  installed  in  accordance  with  national  and  local
codes. Refer to current edition of NFGC in the U.S.
Installations  must  be  made  in  accordance  with  all  authorities  having
jurisdiction.  If  possible,  the  gas  supply  line  should  be  a  separate  line
running directly from meter to furnace. 
NOTE: In the state of Massachusetts:
1. Gas  supply  connections  MUST  be  performed  by  a  licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not
exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used,
they shall be T-handle valves.
4. The  use  of  copper tubing for  gas piping is NOT approved by  the
state of Massachusetts. 
Refer to Table 5 for recommended gas pipe sizing. Risers must be used
to  connect  to  furnace  and  to  meter.  Support  all  gas  piping  with
appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft.
(1.8 M).  Joint  compound  (pipe  dope)  should  be applied  sparingly  and
only to male threads of joints. Pipe dope must be resistant to the action
of propane gas.
 
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-In. W.C.) or less and 
a pressure drop of 0.5-In. W.C. (based on a 0.60 specific gravity gas). Ref: 
Table 7 and 9.2 NFGC.
An  accessible  manual  equipment  shutoff  valve  MUST  be  installed
external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8-in.
(3  mm)  NPT  plugged  tapping,  accessible  for  test  gauge  connection,
MUST  be installed immediately upstream of gas supply connection to
furnace and downstream of manual equipment shutoff valve. 
NOTE: The  furnace gas control  valve inlet  pressure  tap  connection is
suitable to  use as  test gauge connection providing test  pressure DOES
NOT  exceed  maximum  0.5  psig  (14-In.  W.C.)  stated  on  gas  control
valve. (See Fig. 21). 
Some installations require gas entry on right side of furnace (as viewed
in upflow). (See Fig. 22). 
A04167
Fig. 21 – Redundant Automatic Gas Control Valve
A08551
Fig. 22 – Burner and Manifold
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
Use proper length of pipe to avoid stress on gas control manifold and
gas valve.
Gas valve inlet and/or inlet pipe must remain capped until gas supply
line  is  permanently  installed  to  protect  the  valve  from  moisture  and
debris. Also, install a sediment trap in the gas supply piping at the inlet
to the gas valve. 
Table 5 – Maximum Capacity of Pipe
NOMINAL 
IRON PIPE 
SIZE
IN. (MM)
INTERNAL
DIA.
IN. (MM)
LENGTH OF PIPE - FT (M)
10
(3.0) 
20 
(6.0)
30 
(9.1)
40
(12.1)
50
(15.2)
1/2 (12.7)  0.622(158)  175  120  97  82  73 
3/4 (19.0) 0.824 (20.9)  360  250  200  170  151 
1 ( 25.4) 1.049 (26.6)  680  465  375  320  285 
1-1/4 (31.8) 1.380 (35.0)  1400  950  770  660  580 
1-1/2 (38.1)  1.610 (40.9)  2100  1460  1180  990  900 
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage. 
If  local  codes  allow  the  use  of  a  flexible  gas  appliance  connector,
always use a new listed connector. Do not use a connector which has
previously  served  another  gas  appliance.  Black  iron  pipe  shall  be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage. 
Connect gas pipe to furnace using a backup wrench to avoid damaging
gas controls and burner misalignment.
REGULATOR COVER SCREW
PLASTIC ADJUST SCREW
LOW STAGE 
GAS PRESSURE 
REGULATOR ADJUSTMENT
MANIFOLD
PRESSURE TAP
INLET
PRESSURE TAP
ON/OFF SWITCH
REGULATOR SPRING
HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT