PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
42
(9.) Reinstall burner assembly. Center burners in cell openings.
10. Remove old sealant from cell panel and collector box flange.
11. Spray  releasing  agent  on  the  heat  exchanger  cell  panel  where
collector box assembly contacts cell panel. 
NOTE: A releasing agent such as cooking spray or equivalent (must not
contain  corn  or  canola  oil,  aromatic  or  halogenated  hydrocarbons  or
inadequate  seal  may  occur)  and  RTV  sealant  (G.E.  162,  6702,  or
Dow-Corning  738)  are  needed  before  starting  installation.  DO  NOT
substitute  any  other  type  of  RTV  sealant.  G.E.  162  (P771-9003)  is
available through RCD in 3-oz tubes.
12. Apply new sealant to flange of collector box and attach to cell panel
using existing screws, making sure all screws are secure.
13. Reconnect  wires  to  the  following  components  (Use  connection
diagram on wiring label, if wires were not marked for reconnection
locations.):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
14. Reinstall internal vent pipe, if applicable.
15. Reinstall  vent  connector  on  furnace  vent  elbow.  Securely  fasten
vent  connector  to  vent  elbow  with  2  field-supplied,
corrosion-resistant, sheet metal screws located 180_ apart.
16. Replace blower access door only if it was removed.
17. Set  thermostat  above  room  temperature  and  check  furnace  for
proper operation.
18. Verify  blower  airflow  and  speed  changes  between  heating  and
cooling. 
19. Check for gas leaks.
SEQUENCE OF OPERATION
NOTE: Furnace control must be grounded for proper operation or else
control  will  lock  out.  Control  is  grounded  through  green/yellow  wire
routed to gas valve and burner box screw. Using the schematic diagram
in Fig. 59, follow the sequence of operation through the different modes.
Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W/W1 or
W/W1-and-W2),  the  control  will  start  a  90-second  blower-only  ON
period  two  seconds  after  power  is  restored,  if  the  thermostat  is  still
calling for gas heating. The amber LED light will flash code 12 during
the 90-second  period, after  which the  LED  will  be  ON  continuous, as
long as  no faults  are detected. After  the  90-second period,  the furnace
will respond to the thermostat normally. 
The blower door must be installed for power to be conducted through the
blower  door  interlock  switch  ILK  to  the  furnace  control  CPU,
transformer  TRAN,  inducer  motor  IDM,  blower  motor  BLWM,
hot-surface igniter HSI, and gas valve GV. 
1. Two-Stage  Heating  (Adaptive  Mode)  with  Single-Stage
Thermostat. 
See Fig. 28 - Fig. 35 for thermostat connections 
NOTE:  The  low-heat  only  switch  SW1-2  selects  either  the  low-heat
only  operation  mode  when  ON,  (see  item  2.  below)  or  the  adaptive
heating  mode  when OFF  in  response  to  a  call  for  heat.  (See  Fig. 54).
When  the  W2  thermostat  terminal  is  energized  it  will  always  cause
high-heat operation when the R-to-W circuit is closed, regardless of the
setting  of  the  low-heat  only  switch.  This  furnace  can  operate  as  a
two-stage  furnace  with  a  single-stage  thermostat  because  the  furnace
control  CPU  includes  a  programmed  adaptive  sequence  of  controlled
operation, which selects low-heat or high-heat operation. This selection
is  based  upon  the  stored  history  of  the  length  of  previous  gas-heating
periods of the single-stage thermostat. 
The furnace will start up in either low- or high-heat. If the furnace starts
up in low-heat, the control CPU determines the low-heat on-time (from 0
to 16 minutes) which is permitted before switching to high-heat. 
If the power is interrupted, the stored history is  erased and the control
CPU  will  select  low-heat  for  up  to  16  minutes  and  then  switch  to
high-heat,  as  long  as  the  thermostat  continues  to  call  for  heat.
Subsequent selection is based on stored history of the thermostat cycle
times. 
The  wall  thermostat  “calls  for  heat”,  closing  the  R-to-W  circuit.  The
furnace  control  performs  a  self-check,  verifies  the  low-heat  and
high-heat pressure switch contacts LPS and HPS are open, and starts the
inducer motor IDM in high-speed.
a. Inducer Prepurge Period
(1.)  If the furnace control CPU selects low-heat operation the 
inducer motor IDM comes up to speed, the low-heat 
pressure switch LPS closes, and the furnace control CPU 
begins a 15-second prepurge period. If the low-heat pressure 
switch LPS fails to remain closed the inducer motor IDM 
will remain running at high-speed. After the low-heat 
pressure switch re-closes the furnace control CPU will 
begin a 15-second prepurge period, and continue to run the 
inducer motor IDM at high-speed.
(2.) If the furnace control CPU selects high-heat operation, the 
inducer motor IDM remains running at high-speed, and the 
high-heat pressure switch relay HPSR is de-energized to 
close the NC contact. When sufficient pressure is available 
the high-heat pressure switch HPS closes, and the high-heat 
gas valve solenoid GV-HI is energized. The furnace control 
CPU begins a 15-second prepurge period after the low-heat 
pressure switch LPS closes. If the high-heat pressure switch 
HPS fails to close and the low-heat pressure switch LPS 
closes, the furnace will operate at low-heat gas flow rate 
until the high-heat pressure switch closes for a maximum of 
2 minutes after ignition. 
b. Igniter Warm-Up -At the end of the prepurge period, the 
Hot-Surface Igniter HSI is energized for a 17-second igniter 
warm-up period. 
c. Trial-For-Ignition Sequence -When the igniter warm-up period 
is completed the main gas valve relay contact GVR closes to 
energize the gas valve solenoid GV-M. The gas valve solenoid 
GV-M permits gas flow to the burners where it is ignited by the 
HSI. Five seconds after the GVR closes, a 2-second flame 
proving period begins. The HSI igniter will remain energized 
until the flame is sensed or until the 2-second flame proving 
period begins. If the furnace control CPU selects high-heat 
operation, the high-heat gas valve solenoid GV-HI is also 
energized.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections.  A
fire or explosion may result causing property damage, personal injury
or loss of life.