PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
41
Cleaning Heat Exchanger
The following steps should be performed by a qualified service agency.
NOTE:  If  the  heat  exchangers  get  a  heavy  accumulation  of  soot  and
carbon,  they  should  be  replaced  rather  than  trying  to  clean  them
thoroughly. A build-up of soot and carbon indicates that a problem exists
which needs to be corrected,  such as improper adjustment of manifold
pressure,  insufficient  or  poor  quality  combustion  air,  incorrect  size  or
damaged  manifold  orifice(s),  improper  gas,  or  a  restricted  heat
exchanger. Action must be taken to correct the problem. 
If it becomes necessary to clean the heat exchangers because of dust or
corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow  or  horizontal furnace having an  internal vent  pipe,
remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to aid in
reconnection (be careful  when  disconnecting wires  from switches
because damage may occur):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode. 
h. Flame rollout switches.
6. Remove screws  that fasten  the  collector box  assembly  to  the  cell
panel. Be careful not to damage the collector box. Inducer assembly
and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the four screws that attach the burner assembly to the cell
panel. The gas valve and individual burners need not be removed
from support assembly. Remove NOx baffles, if installed.
NOTE:  Be  very  careful  when  removing  burner  assembly  to  avoid
breaking igniter. See Fig. 56 and Fig. 57 for correct igniter location.
A05026
Fig. 56 – Igniter Position - Top View
A05025
Fig. 57 – Igniter Position - Side View
NOTE: The materials needed in item 9 can usually be purchased at local
hardware stores.
9. Using a field-provided 25-caliber rifle cleaning brush; a 36-in. (914
mm)  long,  1/4-in.  (6  mm)  diameter  steel  spring  cable;  and  a
variable speed drill, do the following:
a. Remove metal screw fitting from wire brush to allow insertion 
into cable.
b. Insert the twisted wire end of brush into end of spring cable, and 
crimp tight with crimping tool or crimp by striking with 
ball-peen hammer. TIGHTNESS IS VERY IMPORTANT. After 
crimping:
(1.) Attach variable-speed, reversible drill to the end of spring 
cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of cell and 
slowly rotate with drill. DO NOT force cable. Gradually 
insert cable into upper pass of cell. (See Fig. 58).
A91252
Fig. 58 – Cleaning Heat Exchanger Cell
(3.) Work cable in and out of cell 3 or 4 times to obtain 
sufficient cleaning. DO NOT pull cable with great force. 
Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of cell, and 
proceed to clean 2 lower passes of cell in same manner as 
upper pass.
(5.) Repeat foregoing procedures until each cell in furnace has 
been cleaned.
(6.) Using vacuum cleaner, remove residue from each cell.
(7.) Using vacuum cleaner with soft brush attachment, clean 
burner assembly.
(8.) Clean flame sensor with fine steel wool.
9/32”
7.1mm
5/16”
7.9mm