PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
47
TROUBLESHOOTING GUIDE
 A14311a
Is AMBER LED status light on?  
Is there 24V at SEC-1 and SEC-2?  
Is there 115V at L1 and L2?  
Replace furnace control.  
Is door switch closed?  
Replace transformer.  
Replace door switch.  
Is there 115V going to switch?  
Is door switch closed?  
Is circuit breaker closed?  
Check for continuity in wire from circuit 
breaker to furnace.  
Close circuit breaker and go back to 
START.  
Is AMBER LED status light blinking 
rapidly without a pause?  
Check for correct line voltage polarity.  If 
units are twinned, check for proper low-
voltage (24V) transformer phasing.  
Is AMBER LED status light blinking 
ON/OFF slowly with a combination of 
short and long flashes?  
Determine status code.  The status code 
is a 2 digit number with the first digit 
determined by the number of short 
flashes and the second digit by the 
number of long flashes?  
To recall previous status codes disconnect the R 
thermostat connection, reset power, and put setup 
switch SW1-1 in the ON position.  The AMBER LED 
will flash the status codes in the order of occurrence.  
Record status codes until status code #11 flashes (1 
short and 1 long flash).  After status code #11 
flashes the status codes will repeat.  Status codes 
are erased after 72 hours or can be manually erased 
by putting setup switch SW1-1 in the ON position 
and jumpering R, W/W1, and Y/Y2 simultaneously 
until status code #11 is flashed.  When done put 
setup switch SW1-1 in the OFF position. 
Was there a previous status code other 
than #11?  
Go to section below for the status code 
that was flashed.  
Does the control respond to W/W1, W2, 
Y1, Y/Y2, and G (24V)  thermostat 
signals? 
Run system through a low-heat, high-
heat, or cooling cycle to check operation.  
Status codes are erased after 72 hours 
or can be manually erased by putting 
setup switch SW1-1 in the ON position 
and jumpering R, W/W1, and Y/Y2 
simultaneously until status code #11 is 
flashed. 
Is 24V present at W/W1, W2, Y1, Y/Y2 or 
G thermostat terminals on the furnace 
control? 
Check room thermostat or 
interconnecting cable. 
Disconnect all the thermostat wires from 
the furnace control. 
Does the problem repeat when using a 
jumper wire? 
Replace furnace control. 
The thermostat is not compatible with the 
furnace control.  Either install a ballast 
resistor, connect the Com24V thermostat 
terminal to the thermostat, or replace the 
thermostat. 
YES 
NO 
YES 
YES 
YES 
YES 
YES 
YES YES  YES 
YES 
START 
YES 
YES 
NO 
NO 
NO 
NO NO 
NO 
NO NO 
NO 
NO 
NO 
Troubleshootin
 Guide – Variable Speed 
11  NO PREVIOUS CODE – Status codes are erased after 
72 hours or can be manually erased by putting setup 
switch SW1-1 in the ON position and jumpering R, 
W/W1, and Y/Y2 simultaneously until status code #11 
is flashed.  Run system through a low-heat, high-heat, 
or cooling cycle to check system. 
12  BLOWER ON AFTER POWER UP – (115V OR 24V) – 
Normal operation.  Blower runs for 90 seconds, if unit is 
powered up during a call for heat (R-W/W1 closed) or 
when (R-W/W1 opens) during the blower on-delay 
eriod. 
13  LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, 
draft safeguard, flame rollout, or blocked vent switch (if 
used) is open longer than 3 minutes or 10 successive 
limit trips occurred during high-heat.  Control will auto-
reset after 3 hours.  See code 33. 
14  IGNITION LOCKOUT – System failed to ignite gas and 
prove flame in 4 attempts.  Control will auto-reset after 
3 hours.  See status code 34.