PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28
Air  for  combustion  must  not  be  contaminated  by  halogen  compounds
which  include  chlorides,  fluorides,  bromides,  and  iodides.  These
compounds  are  found  in  many  common  home  products  such  as
detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and
air freshener, and can cause corrosion of furnaces and vents. Avoid using
such  products  in  the  combustion-air  supply.  Furnace  use  during
construction of  the  building  could  cause  the  furnace  to  be  exposed  to
halogen compounds, causing premature failure of the furnace or venting
system due to corrosion. 
Vent dampers on any appliance connected to the common vent can cause
condensation  and  corrosion  in  the  venting  system.  Do  not  use  vent
dampers on appliances common vented with this furnace. 
Additional Venting Requirements
A 4-in. (102 mm) round vent elbow is supplied with the furnace. A 5-in.
(127 mm) or 6- in. (152 mm) vent connector may be required for some
model furnaces. A field-supplied 4-in. (102 mm)  to 5-in. (127 mm) or
4-in. (102 mm) to 6-in. (152 mm) sheet metal increaser fitting is required
when 5-in. (127 mm) or 6-in. (152 mm) vent connector is used. See 
Fig. 38  -  Fig. 50  for  Venting  Orientation  of  approved  vent
configurations. 
NOTE: Vent connector length for connector sizing starts at furnace vent
elbow.  The  4-in.  (102  mm)  vent  elbow  is  shipped  for  upflow
configuration and may be rotated for other positions. Remove the three
screws that secure vent elbow to furnace, rotate furnace vent elbow to
position desired, reinstall screws. The factory-supplied vent elbow does
NOT count as part of the number of vent connector elbows. 
The vent connector can exit the furnace through one of five locations on
the casing.
1. Attach the single wall vent connector to the furnace vent elbow, and
fasten  the  vent  connector  to  the  vent  elbow  with  at  least  two
field-supplied, corrosion-resistant, sheet metal screws located 180_
apart.
NOTE:  An  accessory  flue  extension  is  available  to  extend  from  the
furnace elbow to outside the furnace casing. See Product Data Sheet for
accessory listing. If flue extension is used, fasten the flue extension to
the vent elbow with at least two field-supplied, corrosion-resistant, sheet
metal  screws located 180_ apart.  Fasten  the  vent connector to  the flue
extension with at least two field-supplied, corrosion resistant sheet metal
screws located 180_ apart.
2. Vent  the  furnace  with  the  appropriate  connector.  (See  Fig. 38  -
Fig. 50).
3. Determine the correct location of the knockout to be removed.
4. Use a hammer and screwdriver to strike a sharp blow between the
tie  points  and  work  the  slug  back  and  forth  until  the  slug  breaks
free.
An accessory Vent Guard Kit is REQUIRED for downflow applications
for  use  where  the  vent  exits  through  the  lower  portion  of  the  furnace
casing.  Refer  to  the  Vent  Guard  Kit  Instructions  for  complete  details.
See Product Data Sheet for accessory listing.
The horizontal portion of the venting system shall slope upwards not less
than 1/4-in. per  linear ft. (21 mm/m) from the furnace to the vent and
shall be rigidly supported every 5 ft. (1.5 M) or less with metal hangers
or straps to ensure there is no movement after installation. 
Sidewall Venting
This furnace is not approved for direct sidewall horizontal venting. 
Per section 12.4.3 of the NFPA 54/ANSI Z223.1, any listed mechanical
venter may be used, when approved by the authority having jurisdiction. 
Select  the  listed  mechanical  venter  to  match  the  Btuh  input  of  the
furnace  being  vented.  Follow  all  manufacturer’s  installation
requirements  for  venting  and  termination  included  with  the  listed
mechanical venter. 
Caution!! For the following applications, use the minimum vertical heights as specified below. 
For all other applications, follow exclusively the National Fuel Gas Code. 
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
CAUTION
!
BURN HAZARD
Failure to follow this caution may result in personal injury. 
Hot  vent  pipe  is  within  reach  of  small  children  when  installed  in
downflow position. 
See the following instruction.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury. 
Sheet  metal  parts may have sharp  edges  or  burrs.  Use  care  and wear
appropriate  protective  clothing,  safety  glasses  and  gloves  when
handling parts, and servicing furnaces.
FURNACE
ORIENTATION 
VENT ORIENTATION
FURNACE INPUT
(BTUH/HR) 
MIN. VENT 
DIAMETER
IN. (mm)
*
 
*. 4-in. (102 mm) inside casing or vent guard
MIN. VERTICAL VENT 
HEIGHT
FT. (M)
†
 
†. Including 4 in. (102 mm) vent section(s)
Downflow 
Vent elbow up then left 
Fig.41
110,000 5 (127)  10 (3.0)
Downflow 
Vent elbow left, then up
Fig. 44 
110,000
132,000
5 (127) 12 (3.6)
Downflow 
Vent elbow up, then right
Fig. 45
110,000 5 (127)  10 (3.0)
Horizontal Left 
Vent elbow right, then up
Fig. 46
132,000  5 (127) 7 (2.1)
Horizontal Left 
Vent Elbow up 
Fig. 47 
132,000  5 (127) 7 (2.1)