Installing the AppController   
 
 
 
 
AppController    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  12 
 
To wire ZS sensors to the controller 
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO
2
, or VOC. ZS 
Sensors are wired to the Rnet port on i-Vu® Open controllers. You can use the following ZS sensors: 
  ZS Standard 
  ZS Plus 
  ZS Pro 
  ZS Pro-F 
 
NOTES 
  The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on 
the Rnet port. 
  A control program can use no more than 5 ZS Sensors 
  SPT sensors cannot share the Rnet with other devices. 
  For detailed instructions, see the ZS Sensor Installation Guide.  
 
1  Remove power from the AppController. 
2  Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation. 
Strip about .25 inch (.6 cm) of the inner insulation from each wire. 
 
Outer Jacket
Inner insulation.25 in.
(.6 cm)
 
 
3  Wire each terminal on the sensor to the same terminal on the controller. See diagram below. 
NOTE Carrier recommends that you use the following Rnet wiring scheme: 
 
 
4  Apply power to the AppController.