Installing the AppController
   
 
 
 
AppController    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  15 
 
To wire an Equipment Touch to the AppController 
NOTES 
  The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet. 
  If the Equipment Touch will be: 
○  Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet 
wiring and follow the wiring instructions To wire ZS sensors to the AppController (page 12).  
○  The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet 
cable and follow the instructions below. 
  For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch 
Installation and Setup Guide. 
 
 CAUTION The AppController can share a power supply with the Carrier controller as long as: 
  The power supply is AC power. 
  You maintain the same polarity. 
  You use the power source only for Carrier controllers. 
 
 
1  Turn off the AppController's power. 
2  Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.   
 
 
3  Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.  
4  Wire the AppController's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment 
Touch's connector. 
NOTE  If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal. 
5  Turn on the AppController's power. 
6  Turn on the Equipment Touch.