Troubleshooting   
 
 
 
 
AppController    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  20 
 
Exec halted after frequent system errors, due to: 
  Controller halted 
  Program memory corrupted 
  One or more programs stopped 
Exec start-up aborted, Boot is running 
Firmware transfer in progress, Boot is running 
7 flashes per second, 
alternating with Run LED 
Ten second recovery period after brownout 
14 flashes per second, 
alternating with Run LED 
Failure. Try the following solutions: 
  Turn the AppController off, then on. 
  Download memory to the AppController. 
  Replace the AppController.  
 
 
NOTE If you resolve the issue but the Error LED does not turn off, cycle power to the controller. 
 
 
Serial number 
If you need the AppController's serial number when troubleshooting, the number is on a sticker on the back of the 
main controller board. 
 
 
 
To restore defaults 
 CAUTION This erases all archived information and user-configuration settings. You will have to reconfigure 
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control 
Systems Support. 
  
To erase volatile memory data and restore factory default configuration settings: 
1  Turn off the AppController's power switch. 
2  Put the Factory Defaults jumper on. 
3  Turn on the AppController's power switch. 
4  Remove the Factory Defaults jumper.