ALARM CODE DESCRIPTIONS (continued)
ALARM CODE
RESET TYPE PROBABLE CAUSE
ALARM DESCRIPTION
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
See compressor alarm subcode
Manual
Manual
Manual
Manual
Fault, compressor C1 N°1
Fault, compressor C1 N°nn
Fault, compressor C2 N°1
Fault, compressor C2 N°nn
Fault, compressor C3 N°1
Fault, compressor C3 N°nn
Fault, compressor C4 N°1
Fault, compressor C4 N°nn
Compressor B1 motor temperature too high
Compressor B1 crankcase heater fault
Compressor B1 high pressure switch fault
PTC temperature probe
Compressor motor B1 out of range
C1-01
C1-nn
C2-01
C2-nn
C3-01
C3-nn
C4-01
C4-nn
Process faults
XX-01*
XX-02*
XX-03*
XX-03*
Motor fault, wiring
Crankcase heater defective, wiring fault
Condenser flow rate too low, condenser valve blocked, fan circuit
fault, condenser air or water entering temperature too high
Probe defective