88
0
0
1
16.0
6.0
5.9
5.8
5.7
1 5.7
MODIFYING THE VALUE OF A PARAMETER
OPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE
2-DIGIT DISPLAY 4-DIGIT DISPLAY
Hold on the MENU button until the LED for SETPOINT lights.
Press one of theArrow buttons until the two-digit display shows 1
(item number 1- cooling setpoint 2).
The value for setpoint 2 is displayed in the four-digit display (6.0°C in this
example).
Press the Enter button for more than 2 seconds to enable the value associated
with item 1 to be modified.
The Setpoint menu LED and the two-digit display flash indicating that modification
mode is active.
Keep pressing the DownArrow button until the value 5.7 is displayed in the four-
digit display. The Setpoint menu LED and the two-digit display keep flashing.
Press the Enter button again to validate the change. The new setpoint is 5.7°C.
The Setpoint menu LED and the two-digit display stop flashing, indicating that
modification mode no longer applies.