96
OUTPUTS STATUS & TESTS MENU (continued)
ITEM FORMAT UNITS
10 0to6
tESt
11 b
123
bb
tESt
12 nnn %
tESt
13 nnn %
tESt
14 nnn %
tESt
15 nnn %
tESt
16 nnn %
tESt
17 nnn %
tESt
18 On
Stop
tESt
FAIL
Good
Forc -
19 On
OFF
tESt
FAIL
Good
Forc -
DESCRIPTION
Fan status, circuit C. Permits selection of the fan to be tested.
1=fanC1
2=fanC2
3=fanC3
4=fanC4
5=fanC5
6=fanC6
Alarm status
b1 = alarm relay
b2 = alert relay
b3 = general alarm relay (present if energy management option is used)
EXV A position
0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
EXV B position
0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
EXV C position
0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
Fan speed, circuit A. Only displayed if a variable speed controller is selected in circuitA.
In test mode, this permits selection of the required speed.
Fan speed, circuit B. Only displayed if a variable speed controller is selected in circuit B.
In test mode, this permits selection of the required speed.
Fan speed, circuit C. Only displayed if a variable speed controller is selected in circuit C.
In test mode, this permits selection of the required speed.
Evaporator water pump #1 command status. Not displayed if the unit does not control a pump.
On: pump is running
Stop: pump is stopped
Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the
pump with no delay and for an unlimited length of time. The pump will remain on until any button of the user interface is
pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with "Forc"
if the pump status if forced through CCN.
During the test phase, power to the pump is switched on for 10 seconds only. When the test is completed the following is
displayed:
- Fail: displayed if the test has failed because the pump was not started
- Good: displayed if the test was successful
Evaporator water pump #2 command status. Not displayed if the unit does not control a secondary pump.
On: pump is running
Stop: pump is stopped
Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the
pump with no delay and for an unlimited length of time. The pump will remain on until any button of the user interface is
pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with "Forc"
if the pump status if forced through CCN.
During the test phase, ...as above
SUBMENU OUTPUTS 2 (SELECTION)
ITEM FORMAT UNITS
0 OUtPUts 2 Menu
1
On
OFF
Forc
tESt
FAIL
Good
2b
12
b
3b
1
b
2
b
3
4 nnn %
tESt
5b
1
b
2
bb
34
6b
1
b
2
bb
34
70to4
tESt
DESCRIPTION
When selected this item authorises return to the previous menu.
Heat reclaim condenser pump status. Only displayed when the heat reclaim option is selected.
Forc: This item is only displayed when the unit is in Local off (LOFF) mode. Selecting this item permits starting up the pump
whithout delay and for an unlimited period. The pump stays on until any button on the user interface is pressed: it is then
immediately stopped. If the unit is under CCN control, the pump status is displayed alternatively with ‘Forc’, if the status is forced
by CCN.
Heat exchanger heater status (b1) and heat reclaim condenser heater status (b2).
Hot gas bypass valve status. Only displayed if the hot gas bypass option is selected.
b1 = hot gas bypass valve, circuitA
b2 = hot gas bypass valve, circuit B
b3 = hot gas bypass valve, circuit C
Heat reclaim condenser water valve position. Only displayed if the heat reclaim option is selected.
Heat reclaim operation valve status, circuit A.
b1 = air condenser entering valve, circuitA
b2 = water condenser entering valve, circuit A
b3 = air condenser leaving valve, circuitA
b4= water condenser leaving valve, circuitA
Heat reclaim operation valve status, circuit B.
b1 = air condenser entering valve, circuit B
b2 = water condenser entering valve, circuit B
b3 = air condenser leaving valve, circuit B
b4= water condenser leaving valve, circuit B
Additional heating stage status.
1 = stage 1
2 = stage 2
3 = stage 3
4 = stage 4