33
8.3 RECOMMENDED WIRE SIZE
Model
Main power supply to
CDU unit [R-Y-B-N] +
Earth
Power Supply from
CDU to Indoor unit
[P N] + Earth
Power
Supply
from Master
CDU to Slave
CDU
[
R-Y-B
-
N
]
+
Earth
Communicati
on wire 2
core twisted
and shielded
7 HP
6 mm² / 4 core
+ 2.5 mm² / 1 core
2.5 mm² / 2 core +
2.5 mm² / 1 core
NA
1.0 mm²
11 HP
6 mm² / 4 core
+ 2.5 mm² / 1 core
2.5 mm² / 2 core +
2.5 mm² / 1 core
NA
1.0 mm²
14 HP
10 mm² / 4 core
+ 2.5 mm² / 1 core
2.5 mm² / 2 core +
2.5 mm² / 1 core
NA
1.0 mm²
22 HP
16 mm² / 4 core
+ 16 mm² / 1 core
2.5 mm² / 2 core +
2.5 mm² / 1 core
6 mm² / 4 core
+ 6 mm² / 1 core
1.0 mm²
Note: Ensure stable incoming power supply and unit is properly grounded.