EasyManua.ls Logo

Carrier CDII-184R1-0CTR4 - Applied Control and Functions (Including Circuit Configurations); CDU PCB Details

Carrier CDII-184R1-0CTR4
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
9. Applied Control & Functions (Including circuit configurations)
9.1 CDU PCB DETAILS
Parts
Legend
Description
CDU PCB
Fuse 1 (F1)
Type
Glass tube Slow glow fuse
Length
20.16 mm
Rating
250 Volt ,3.15 Ampere
Fuse 2 (F2)
Type
Glass tube Slow glow fuse
Length
31.82 mm
Rating
250 Volt ,7 Ampere
Connector Screw M3
Max. Torque
0.8 N/m
Connector Screw M4
Max. Torque
1.8 N/m
Note:
Fuse 1 (F1) is for protection of PCB power supply, it protects power supply section from extreme
high voltage and high electrical surges.
Fuse 2 (F2) is for protection of PCB due to wrong connection on Fan motor, or any fault occurred at
fan motor.
Don’t replace the PCB due to fuse failure only.
Replace faulty fuse with the appropriate fuse as per give details in table.