Carrier Omnizone 50BVC - Page 81

Carrier Omnizone 50BVC
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81
C1_HAND R Discrete Input 9 comp1_hand BV 151 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C2_FAIL R Discrete Input 10 comp2_fail BV 154 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C2_HAND R Discrete Input 11 comp2_hand BV 155 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C3_FAIL R Discrete Input 12 comp3_fail BV 157 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C3_HAND R Discrete Input 13 comp3_hand BV 158 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C4_FAIL R Discrete Input 14 comp4_fail BV 160 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C4_HAND R Discrete Input 15 comp4_hand BV 161 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
CMP1_RNTM R Discrete Input 16 comp1_rntm BV 35 Select
Compressor 1 Runtime
Alarm Status, (8760
Hours)
0 = Off
1 = Timer Has Expired
CMP2_RNTM R Discrete Input 17 comp2_rntm BV 36 Select
Compressor 2 Runtime
Alarm Status, (Hours)
0 = Off
1 = Timer Has Expired
CMP3_RNTM R Discrete Input 18 comp3_rntm BV 69 Select
Compressor 3 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CMP4_RNTM R Discrete Input 19 comp4_rntm BV 71 Select
Compressor 4 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CO2 Sensor Ena R/W
Holding Regis-
ter (Float)
9
co2_sen-
sor_ena
AV 26 Select
Zone CO
2
Sensor
Enable Setup
0 = No CO
2
(Default)
1 = CO
2
Monitoring
2 = CO
2
+ Damper
3 = CO
2
BAS Monitoring
4 = CO
2
BAS + Damper
5 = Open Damper as Fan
runs
Coil Configuration
Status
R
Input Register
(Float)
3
coil_cfg_sta-
tus
AV 150 Select
Network Status of Coil
Configuration
0 = Parallel
1 = Series
Comp Stage1 Out-
put Cmd
R Discrete Input 20
cmp_stg1_cm
d
BV 11
nvoC-
mp1Cmd
SNVT_switch(95)
Compressor Stage 1
Output Status
0 = Compressor Stage 1
Off
1 = Compressor 1 On
Comp Stage2 Out-
put Cmd
R Discrete Input 21
cmp_stg2_cm
d
BV 12
nvoC-
mp2Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 2 Off
1 = Compressor 2 On
Comp Stage3 Out-
put Cmd
R Discrete Input 22
cmp_stg3_cm
d
BV 66
nvoC-
mp3Cmd
SNVT_switch(95)
Compressor Stage 3
Output Status
0 = Compressor 3 Off
1 = Compressor 3 On
Comp Stage4 Out-
put Cmd
R Discrete Input 23
cmp_stg4_cm
d
BV 67
nvoC-
mp4Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 4 Off
1 = Compressor 4 On
Table 66 — Integration Points List (cont)
PROTOCOL MAP MODBUS BACNET LONWORKS OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME SNVT DESCRIPTION