81
C1_HAND R Discrete Input 9 comp1_hand BV 151 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C2_FAIL R Discrete Input 10 comp2_fail BV 154 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C2_HAND R Discrete Input 11 comp2_hand BV 155 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C3_FAIL R Discrete Input 12 comp3_fail BV 157 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C3_HAND R Discrete Input 13 comp3_hand BV 158 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
C4_FAIL R Discrete Input 14 comp4_fail BV 160 Select
Network Alarm indicat-
ing compressor com-
manded to run but no
current feedback is
sensed
C4_HAND R Discrete Input 15 comp4_hand BV 161 Select
Network Alarm indicat-
ing compressor is run-
ning but the controller is
not issuing an automatic
command.
CMP1_RNTM R Discrete Input 16 comp1_rntm BV 35 Select
Compressor 1 Runtime
Alarm Status, (8760
Hours)
0 = Off
1 = Timer Has Expired
CMP2_RNTM R Discrete Input 17 comp2_rntm BV 36 Select
Compressor 2 Runtime
Alarm Status, (Hours)
0 = Off
1 = Timer Has Expired
CMP3_RNTM R Discrete Input 18 comp3_rntm BV 69 Select
Compressor 3 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CMP4_RNTM R Discrete Input 19 comp4_rntm BV 71 Select
Compressor 4 Runtime
Alarm Status (Hours)
0 = Off
1 = Timer Has Expired
CO2 Sensor Ena R/W
Holding Regis-
ter (Float)
9
co2_sen-
sor_ena
AV 26 Select
Zone CO
2
Sensor
Enable Setup
0 = No CO
2
(Default)
1 = CO
2
Monitoring
2 = CO
2
+ Damper
3 = CO
2
BAS Monitoring
4 = CO
2
BAS + Damper
5 = Open Damper as Fan
runs
Coil Configuration
Status
R
Input Register
(Float)
3
coil_cfg_sta-
tus
AV 150 Select
Network Status of Coil
Configuration
0 = Parallel
1 = Series
Comp Stage1 Out-
put Cmd
R Discrete Input 20
cmp_stg1_cm
d
BV 11
nvoC-
mp1Cmd
SNVT_switch(95)
Compressor Stage 1
Output Status
0 = Compressor Stage 1
Off
1 = Compressor 1 On
Comp Stage2 Out-
put Cmd
R Discrete Input 21
cmp_stg2_cm
d
BV 12
nvoC-
mp2Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 2 Off
1 = Compressor 2 On
Comp Stage3 Out-
put Cmd
R Discrete Input 22
cmp_stg3_cm
d
BV 66
nvoC-
mp3Cmd
SNVT_switch(95)
Compressor Stage 3
Output Status
0 = Compressor 3 Off
1 = Compressor 3 On
Comp Stage4 Out-
put Cmd
R Discrete Input 23
cmp_stg4_cm
d
BV 67
nvoC-
mp4Cmd
SNVT_switch(95)
Compressor Stage 2
Output Status
0 = Compressor 4 Off
1 = Compressor 4 On
Table 66 — Integration Points List (cont)
PROTOCOL MAP MODBUS BACNET LONWORKS OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME SNVT DESCRIPTION