a. Remove the indoor pipe flare nut. ( Check that there is no debris inside. )
b. Align the center of the flare surface, and tighten the indoor pipe union and connection pipe
flare nut with a torque wrench or double-ended wrench. ( Figure. 14 )
While aligning the center of the flare surface, tighten the nut by hand, hold the union side with a
wrench and tighten the nut according to the specified tightening torque with a torque wrench.
Torque wrench or
double-ended wrench
Outdoor side
Indoor side
Figure
14
Pay careful attention to the following points when installing the refrigerant pipes.
Hold the pipe with one wrench while tightening the connections with a torque
wrench or double-ended wrench.
Be careful not to damage the flare nut threads.
If the tightening torque is insufficient, gas will leak from the connection.
If it is too strong, the flare will be damaged.
Tighten the nut with the torque shown in Table 1.
Do not bend the pipe more than three times at one place.
When extending the rolled pipe, straighten the pipe by unwinding as shown in Figure 13.
Figure
13
Repeat the procedure for flaring the tube to connect to the outdoor unit.
Tighten the flare nut of the connection pipe at the outdoor unit valve. ( Figure. 15 )
27
123456789012345678901234567890121234567890123456789012345678901212345678
1
2345678901234567890123456789012123456789012345678901234567890121234567
8
1
2345678901234567890123456789012123456789012345678901234567890121234567
8
1
2345678901234567890123456789012123456789012345678901234567890121234567
8
123456789012345678901234567890121234567890123456789012345678901212345678
1) Connecting Pipe to the Indoor Unit
234567890123456789012345678901212345678901234567890123456789012123456789012345
234567890123456789012345678901212345678901234567890123456789012123456789012345
234567890123456789012345678901212345678901234567890123456789012123456789012345
2) Connecting the Interconnecting Pipe to the Outdoor Unit Valve
Flare nut Tightening torque(kgf-cm)
6.35mm (1/4) 150 ~ 200
12.7mm (1/2) 500 ~ 550
15.88mm (5/8) 700 ~ 760
Table 1