Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
36
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Modbus Register Type
Modbus
Register #
13=IGC Override
Supply Air
Temperature
R °F sa_temp AV:1008 Input Register (Float) 109
DCV Max Ctrl
Setpoint
R/W ppm 650 iaq_stpt_max AV:3013
Holding Register
(Float)
45
Occ Relative
Humidity Setpoint
R/W %rh 60 occ_dehum_stpt AV:3011
Holding Register
(Float)
83
Occupancy Status R
0=Unoccupied
1=Occupied
occ_status BV:2008 Discrete Input 18
Optimal Start
Type
R/W
1=None
2=Temp
Compensated
3=Learning
Adaptive
2 start_type MSV:2009
Holding Register
(Signed)
154
Setpoint R/W °F unocc_ht_stpt AV:3004
Holding Register
(Float)
17
Economizer Test
R/W
%Open
0
econ_test
AV:81001
Space Relative
Humidity Sensor
R
0=Normal
1=Alarm
sprh_sensor_fail BV:7022 Discrete Input 45
Setpoint
Adjustment
R °F stpt_adj AV:1006 Input Register (Float) 99
Effective Heat
Setpoint
R °F eff_ht_stpt AV:3006 Input Register (Float) 57
Low Fan Econ Min
Pos
R/W %Open 33 econ_min_2 AV:9030
Holding Register
(Float)
89
Fire / Smoke
Shutdown
R
0=Normal
1=Alarm
fire_alarm BV:7007 Discrete Input 32
Reset Filter Alarm R/W
0=Off
1=On
Inactive (0) filter_rntm_clr BV:7517 Coil 22
Setpoint R/W °F unocc_cl_stpt AV:3003
Holding Register
(Float)
15
ZS Sensor
Configuration
R
0=Normal
1=Alarm
zs_config_fail BV:7055 Discrete Input 63
Space Relative
Humidity
R %rh space_rh AV:1011 Input Register (Float) 103
Outdoor Air
Temperature
R °F oa_temp AV:1003 Input Register (Float) 87
Cooling Lockout
Temperature
R/W °F 45 oat_cl_lockout AV:9002
Holding Register
(Float)
43
Power Exhaust
Setpoint
R/W %Open 50 pexh_stpt AV:3010
Holding Register
(Float)
97
BAS On / Off R/W
1=Inactive
2=Occupied
3=Unoccupied
1 keypad_ovrde MSV:1001
Holding Register
(Signed)
133
System Space AQ R/W ppm -999 system_iaq AV:1903
Holding Register
(Float)
149
System Space RH R/W % -999 system_rh AV:1904
Holding Register
(Float)
151
Compressor
Status
R
0=Normal
1=Alarm
comp_alarm BV:7013 Discrete Input 30
Filter Service
Alarm Timer
R/W hr 600 filter_service_hrs AV:2019
Holding Register
(Float)
67
Indoor Air Quality
Sensor
R
0=Normal
1=Alarm
iaq_sensor_fail BV:7039 Discrete Input 37
Heating Lockout
Temperature
R/W °F 65 oat_ht_lockout AV:9003
Holding Register
(Float)
69
Dehumidification
R
0=Inactive
dehum
BV:2006
Discrete Input
9

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals