Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
37
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Modbus Register Type
Modbus
Register #
1=Active
Reversing Valve
Relay State
R
0=Off
1=On
aux_1 BV:2007 Discrete Input 20
Password
Protected Output
Variable
R/W 0 ppo AV:90000
Vent Dmpr Pos /
DCV Min Pos
R/W %Open 20 econ_min AV:9005
Holding Register
(Float)
131
Filter R
0=Clean
1=Dirty
filter_alarm BV:7017 Discrete Input 31
Safety Chain R
0=Normal
1=Alarm
safety_alarm BV:7024 Discrete Input 43
Unocc Relative
Humidity Setpoint
R/W %rh 95 unocc_dehum_stpt AV:3012
Holding Register
(Float)
129
Setpoint R/W °F occ_ht_stpt AV:3002
Holding Register
(Float)
19
Supply Air Temp
Sensor
R
0=Normal
1=Alarm
loc_sat_sensor_fail BV:7020 Discrete Input 51
Override Time
Remaining
R min ovrde_time AV:2016 Input Register (Float) 93
Setpoint
Adjustment
R/W
0=Disable
1=Enable
Active (1) stpt_adj_enable BV:1013 Coil 26
System Space
Temperature
R/W °F -999 system_spt AV:1902
Holding Register
(Float)
123
Space
Temperature
Offset Pot
R °F stpt_adj_offset AV:91006
System Outdoor
AQ
R/W ppm -999 system_oaq AV:1908
Holding Register
(Float)
155
Outdoor Air Temp
Sensor
R
0=Normal
1=Alarm
oat_fail BV:7029 Discrete Input 27
SPT Sensor R
0=Normal
1=Alarm
spt_sensor_fail BV:7032 Discrete Input 38
Fan / Speed R
1=Off
2=Low
3=Med
4=High
5=On
fan_run MSV:2004
Input Register
(Signed)
175
Setpoint
Adjustment Range
R/W °^F 5 stpt_adj_range AV:9015
Holding Register
(Float)
101
Enthalpy (BACnet) R/W
0=High
1=Low
Active (1) oae BV:1901 Coil 6
Optimal Start R/W hr 1 optm_start AV:9026
Holding Register
(Float)
147
System Cooling
Demand Level
R cool_demand_level AV:9006
System Heating
Demand Level
R heat_demand_level AV:9036
System OAT
Master
R °F mstr_oa_temp AV:80001
T5x Override
Duration
R/W hr 1 ovr_dur AV:9023
VFD Speed Test
R/W
%
0
vfd_spd_test
AV:81002
input_3 R
0=Off
1=On
di_3 BI:1003
input_4 R
0=Off
1=On
di_4 BI:1004

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals