Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
41
Access
Value
ID
Register #
4=Filter Status
5=Remote
Occupancy
6=Door Contact
Configuration
R/W
2=NC
1 di9_type MSV:81019
Number Of Heat
Stages
R/W
2=2
2 heat_stages MSV:91004
Occupancy
Source
R/W
Occupied
2=BACnet
Schedule
3=BAS On/Off
4=Remote Occ
1 occ_source MSV:1002
Space sensor type R/W
2=T56
3=SPT Sensor
4=None
1 spt_type MSV:9001
Space Temp
Source
R
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
spt_status MSV:2003
Unit Type R/W
2=LC
WeatherExpert
3=HP O/B Ctrl
4=HP Y1/W1 Ctrl
2 unit_type MSV:9018
ZS Temp Sensor R
1=Alarm
zst_sensor_fail BV:7051
Operation
R
1=Fault Detected
econ_opr BV:7054
Temperature
Alarm Status
R
0=Normal
1=Alarm
spt_alrm_status BV:7056
SPT Sensor R °F
temp
AI:1
SPT Sensor R min
time_remaining
AV:1
Analog 1 Control
R/W % 0 ao1_fac_test AV:91001
OAT Lockout
Temp
R/W °F 75 oat_ec_lockout AV:9008
SAT
R/W °F 120 sat_ht_max AV:83004
Runtime
R hr comp2_rntm AV:2018
Damper Position
R % link_max_dmpr AV:2611
Air Temp
R °F link_sat AV:2608