Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
42
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Modbus Register Type
Modbus
Register #
Output
Air Source
Outdoor Air Temp
R °F link_ahu_oat AV:2609
Stage 3 SAT Stpt
R/W
°F
56
stg_3_sat
AV:83010
Stage 1 SAT Stpt
R/W
°F
57
stg_1_sat
AV:83008
HP Aux Heat
Lockout Temp
R/W °F 40 oat_auxht_lockout AV:3025
input_1
R
ai_1
AI:1001
Factory Test
Analog 2 Control
R/W V 0 ao2_fac_test AV:91002
Compressor 2
Service Alarm
Timer
R/W hr 0 comp2_service_hrs AV:83007
Compressor 1
Service Alarm
Timer
R/W hr 0 comp1_service_hrs AV:83006
Compressor 1
Runtime
R hr comp1_rntm AV:2017
Min VFD Output
R/W
%
40
min_vfd_spd
AV:3027
Stage 2 SAT Stpt
R/W
°F
57
stg_2_sat
AV:83009
slidepot voltage
reading
R slidepot_volts AI:1012
Filter Runtime
R
hr
filter_rntm
AV:2015
Fan Off Delay
R/W
seconds
90
fan_delay_off
AV:9024
input_7
R
°F
ai_7
AI:1007
input_11
R
ai_11
AI:1011
input_2
R
ai_2
AI:1002
Minimum Cooling
SAT
R/W °F 50 sat_cl_min AV:83003
Power Fail Restart
Delay
R/W seconds 5 start_delay AV:9007
Holding Register
(Float)
127
Supply Fan
Service Alarm
Timer
R/W hr 0 sfan_service_hrs AV:83005
Supply Fan
Runtime
R hr sfan_rntm AV:2014
Indoor Air Quality
CO2 (ppm)
R ppm iaq AV:1009 Input Register (Float) 73
Supply Fan VFD
R
%
vfd_output
AV:2027
Indoor Air Quality R
0=Normal
1=Alarm
iaq_alarm BV:7005 Discrete Input 33
Supply Air
Temperature
R
0=Normal
1=Alarm
sat_alarm BV:7004 Discrete Input 47
Space Relative
Humidity
R
0=Normal
1=Alarm
sprh_hi_alarm BV:7018 Discrete Input 34
Space Temp
Sensor
R
0=Normal
1=Alarm
spt_fail BV:7001 Discrete Input 46
Outdoor Air
Quality CO2 (ppm)
R ppm oaq AV:1012 Input Register (Float) 85
Gas Valve R
0=Normal
1=Alarm
igc_alarm BV:7050 Discrete Input 40
Setpoint R/W °F occ_cl_stpt AV:3001
Holding Register
(Float)
9

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals