Reset Conguration Menu – RESETCFG
No. Name Status Default Unit Displayed text* Description
1 cr_sel 0 to 4 0 - Cooling Reset Select Cooling reset selection
2 hr_sel 0 to 4 0 - Heating Reset Select Not applicable to this unit
3 0=None, 1=OAT 0 = None, 1 = OAT
4 2=Delta T, 4=Space Temp 2 = Delta T, 4 = Space temperature
5 3=4-20mA control 3 = 4-20mA control
6
7 Cooling Cooling
8 oat_crno -10 to 51.7 -10 °C OAT No Reset Value OAT, no reset value
9 oat_crfu -10 to 51.7 -10 °C OAT Full Reset Value OAT, full reset value
10 dt_cr_no 0 to 14 0 K Delta T No Reset Value Delta T, no reset value
11 dt_cr_fu 0 to 14 0 K Delta T Full Reset Value Delta T, max. reset value
12 v_cr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
13 v_cr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
14 spacr_no -10 to 51.7 -10 °C Space T No Reset Value Space temperature, no reset value
15 spacr_fu -10 to 51.7 -10 °C Space T Full Reset Value Space temperature, max. reset value
16 cr_deg -16.7 to 16.7 0 K Cooling Reset Deg. Value Maximum cooling reset value
17
18 Heating Not applicable to this unit
19 oat_hrno -10 to 51.7 -10 °C OAT No Reset Value Not applicable to this unit
20 oat_hrfu -10 to 51.7 -10 °C OAT Full Reset Value Not applicable to this unit
21 dt_hr_no 0 to 14 0 K Delta T No Reset Value Not applicable to this unit
22 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Not applicable to this unit
23 v_hr_no 0 to 20 0 mA Current No Reset Value Not applicable to this unit
24 v_hr_fu 0 to 20 0 mA Current Full Reset Value Not applicable to this unit
25 spahr_no -10 to 51.7 -10 °C Space T No Reset Value Not applicable to this unit
26 spahr_fu -10 to 51.7 -10 °C Space T Full Reset Value Not applicable to this unit
27 hr_deg -16.7 to 16.7 0 K Heating Reset Deg. Value Not applicable to this unit
*Depends on the selected language (English by default).
Schedule Menu – SCHEDULE
No. Name Displayed text* Description
1 OCCPC01S OCCPC01S - Schedule Menu Unit on/o time schedule
2 OCCPC02S OCCPC02S - Schedule Menu Unit setpoint selection time schedule
*Depends on the selected language (English by default).
Holiday Menu – HOLIDAY
No. Name Status Default Displayed text* Description
1 HOL_MON 0-12 0 Holiday Start Month Holiday start month
2 HOL_DAY 0-31 0 Start Day Holiday start day
3 HOL_LEN 0-99 0 Duration (days) Holiday duration (days)