31
NOTES:
1. There is a 3 second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will
be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Table 14 — IGC Board LED Alarm Codes
LED
FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
On Normal Operation — — —
Off Hardware Failure No gas heating. —
Loss of power to the IGC. Check 5 amp 
fuse on IGC, power to unit, 24V circuit 
breaker, transformer, and wiring to the 
IGC.
2 Flashes Limit Switch Fault
Gas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or heat 
call (W) Off.
High temperature limit switch is open. 
Check the operation of the indoor 
(evaporator) fan motor.
Ensure that the supply-air temperature rise 
is within the range on the unit nameplate. 
Check wiring and limit switch operation.
3 Flashes Flame Sense Fault Indoor fan and inducer On.
Flame sense normal. Power 
reset for LED reset.
The IGC sensed a flame when the gas 
valve should be closed. Check wiring, 
flame sensor, and gas valve operation.
4 Flashes
Four Consecutive Limit
Switch Fault
No gas heating.
Heat call (W) Off. Power reset 
for LED reset.
4 consecutive limit switch faults within a 
single call for heat. See Limit Switch Fault.
5 Flashes Ignition Fault No gas heating.
Heat call (W) Off. Power reset 
for LED reset.
Unit unsuccessfully attempted ignition for 
15 minutes. Check igniter and flame sensor 
electrode spacing, gaps, etc. Check flame 
sense and igniter wiring. Check gas valve 
operation and gas supply. Check gas valve 
connections to IGC terminals. BRN lead 
must be on Pin 11.
6 Flashes Induced Draft Motor Fault
If heat off: no gas heating.
If heat on: gas valve Off and 
inducer On.
Inducer sense normal, or heat 
call (W) Off.
Inducer sense On when heat call Off, or 
inducer sense Off when heat call On. 
Check wiring, voltage, and operation of 
IGC motor. Check speed sensor wiring to 
IGC.
7 Flashes Rollout Switch Lockout
Gas valve and igniter Off.
Indoor fan and inducer On.
Power reset.
Rollout switch has opened. Check gas 
valve operation. Check induced-draft 
blower wheel is properly secured to motor 
shaft.
8 Flashes Internal Control Lockout No gas heating. Power reset.
IGC has sensed internal hardware or 
software error. If fault is not cleared by 
resetting 24 v power, replace the IGC.
9 Flashes Temporary Software Lockout No gas heating.
1 hour auto reset, or power 
reset.
Electrical interference is disrupting the IGC 
software.