38
Fig. 50 — CO
2
 Sensor Wiring
INTERFACE OVERVIEW
This section describes how to use the EconoMi$er
®
 user interface
for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 51) to scroll through the
menus and menu items, select menu items, and to change parame-
ter and configuration settings.
To use the keypad when working with menus:
• Press the  ▲  (Up  arrow) button to move to  the  previous
menu.
• Press  the  ▼  (Down  arrow)  button  to  move  to  the  next
menu.
• Press the   (Enter) button to display the first item in the
currently displayed menu.
• Press the   (Menu Up/Exit) button to exit a menu’s item
and return to the list of menus.
Fig. 51 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and Ad-
vanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the   (Enter) button to display the first item in the
currently displayed menu.
3. Use the ▲ and ▼ buttons to scroll to the desired parameter.
4. Press the   (Enter) button to display the value of the cur-
rently displayed item.
5. Press the ▲ button to increase (change) the displayed param-
eter value.
6. Press the ▼ button to decrease (change) the displayed param-
eter value.
NOTE:  When  values  are  displayed,  pressing  and  holding  the
▲or ▼ button causes the display to automatically increment or
decrement.
1. Press the   (Enter) button to accept the displayed value and
store it in nonvolatile RAM. “CHANGE STORED” displays.
2. Press  the   (Enter) button  to  return to the  current  menu
parameter.
3. Press the   (Menu Up/Exit) button to return to the previous
menu.
Menu Structure
Table 19 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er
®
 X system.
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
NOTE:  Some  parameters  in  the  menus  use  the  letters  MA  or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor locat-
ed after the cooling coil, in the fan section, where it is designated
as (Cooling) Supply Air Temperature or SAT sensor.
SETUP AND CONFIGURATION
Before being placed into service, the W7220 Economizer module
must be set up and configured for the installed system.
The setup process uses a hierarchical menu structure that is easy to
use. Press the ▲ and ▼ arrow buttons to move forward and back-
ward through the menus and press the button to select and confirm
setup item changes.
Time-Out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD dis-
plays a screen saver, which cycles through the Status items. Each
Status  items  displays  in  turn  and  cycles  to  the  next  item  after
5 seconds.
CO
2
 SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY.  PROVIDE DISCONNECT 
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
IMPORTANT:  During  setup,  the  economizer  module  is
live at all times.