EasyManua.ls Logo

Carrier WeatherExpert 48LCD05 - Page 64

Carrier WeatherExpert 48LCD05
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64
To convert BHP to watts, use 84% motor efficiency. To convert BHP to watts, use 84% motor efficiency.
Table B — 48LC**04 Direct Drive (Horizontal)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
750 0.39 0.19
900 0.18 0.14
1050
1125
1200
1275
1350
1425
1500
2
750 0.69 0.26
900 0.45 0.23
1050 0.22 0.20
1125 0.12 0.19
1200 0.05 0.17
1275
1350
1425
1500
3
750 1.28 0.44
900 1.11 0.46
1050 0.88 0.45
1125 0.75 0.44
1200 0.63 0.44
1275 0.50 0.44
1350 0.38 0.41
1425 0.25 0.39
1500 0.13 0.38
4
750 1.30 0.45
900 1.17 0.48
1050 1.04 0.52
1125 0.97 0.54
1200 0.91 0.56
1275 0.84 0.58
1350 0.76 0.60
1425 0.68 0.61
1500 0.60 0.62
5
750 1.31 0.45
900 1.18 0.48
1050 1.05 0.52
1125 0.99 0.54
1200 0.92 0.56
1275 0.86 0.59
1350 0.80 0.61
1425 0.74 0.64
1500 0.68 0.66
Table C — 48LC**04 Direct Drive (Vertical)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
750 0.27 0.15
900 0.07 0.11
1050
1125
1200
1275
1350
1425
1500
2
750 0.54 0.21
900 0.29 0.18
1050 0.06 0.16
1125
1200
1275
1350
1425
1500
3
750 1.15 0.42
900 0.96 0.43
1050 0.70 0.40
1125 0.55 0.40
1200 0.41 0.39
1275 0.27 0.39
1350
1425
1500
4
750 1.19 0.43
900 1.06 0.46
1050 0.91 0.50
1125 0.83 0.53
1200 0.75 0.55
1275 0.66 0.56
1350 0.56 0.57
1425
1500
5
750 1.21 0.42
900 1.07 0.46
1050 0.93 0.50
1125 0.86 0.52
1200 0.79 0.55
1275 0.71 0.57
1350 0.63 0.59
1425 0.56 0.62
1500 0.47 0.64