EasyManua.ls Logo

Carrier WeatherExpert 48LCD05 - Page 65

Carrier WeatherExpert 48LCD05
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
To convert BHP to watts, use 84% motor efficiency. To convert BHP to watts, use 84% motor efficiency.
Table D — 48LC**05 Direct Drive (Horizontal)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1000 0.12 0.14
1200 0.00 0.21
1400
1500
1600
1700
1800
1900
2000
2
1000 0.89 0.43
1200 0.60 0.40
1400 0.30 0.36
1500 0.16 0.34
1600 0.02 0.32
1700
1800
1900
2000
3
1000 1.14 0.52
1200 0.96 0.59
1400 0.70 0.65
1500 0.54 0.64
1600 0.37 0.61
1700 0.18 0.61
1800
1900
2000
4
1000 1.15 0.52
1200 1.01 0.59
1400 0.86 0.65
1500 0.79 0.69
1600 0.72 0.72
1700 0.64 0.75
1800 0.56 0.79
1900 0.47 0.82
2000 0.37 0.84
5
1000 1.15 0.53
1200 1.02 0.60
1400 0.88 0.67
1500 0.81 0.70
1600 0.74 0.74
1700 0.67 0.78
1800 0.59 0.82
1900 0.51 0.86
2000 0.42 0.92
Table E — 48LC**05 Direct Drive (Vertical)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1000 0.08 0.11
1200
1400
1500
1600
1700
1800
1900
2000
2
1000 0.79 0.37
1200 0.49 0.34
1400 0.20 0.31
1500 0.05 0.29
1600
1700
1800
1900
2000
3
1000 1.11 0.50
1200 0.90 0.57
1400 0.59 0.62
1500 0.40 0.59
1600 0.20 0.52
1700
1800
1900
2000
4
1000 1.12 0.50
1200 0.95 0.57
1400 0.79 0.63
1500 0.70 0.67
1600 0.61 0.70
1700 0.52 0.73
1800 0.41 0.75
1900 0.30 0.77
2000
5
1000 1.13 0.51
1200 0.97 0.58
1400 0.81 0.65
1500 0.73 0.68
1600 0.64 0.72
1700 0.55 0.75
1800 0.46 0.79
1900 0.35 0.82
2000 0.25 0.89
APPENDIX C FAN DATA

Table of Contents

Related product manuals